Data Sheet for Product
Siemens Building Technologies, Inc.  Page 3 of 6 
Document No. 127-0020 
Table 2. Operating Mode (Point 06). 
Value Mode 
0 Unoccupied 
1 Occupied 
2 Override 
3  Occupied – Load Shed. Allows the Water Source 
Heat Pump to distribute the heating/cooling Set Points 
based on the load shed level set at the WSHP 
controller. 
4  Occupied – Load Shed. Allows the Water Source 
Heat Pump to distribute the heating/cooling Set Points 
based on the load shed level set at the WSHP 
controller. 
5 Fan Only 
8 Compressor Off 
9 Unit Shutdown 
190  Off – Condensate Overflow 
191  Off – Brownout 
204  Off – Room Temperature Sensor Fail 
205  Off – Low Discharge Air Temperature 
206  Off – Low Refrigerant Pressure 
207  Off – High Refrigerant Pressure 