Data Sheet for Product
Page 4 of 6  Siemens Building Technologies, Inc. 
  Document No. 127-0020 
Table 3. Warnings Mode (Point 13). 
Value Mode 
0  No Loop Flow Requested 
1 Room Too Warm 
2  Room Too Cool 
4 Change Filter 
8 Rapid Cycling 
16  Bad DAT Sensor 
32  Bad LWT Sensor 
64 Unused 
128  Request Loop Flow 
Table 4. Faults (Points 14 and 15). 
Value Mode 
204  Room Temperature Sensor Fail 
205  Low Discharge Air Temperature 
206  Low Refrigerant Pressure 
207  High Refrigerant Pressure 
255 None 
Table 5. Auto/Manual Mode (Point 27). 
Value Mode 
0 Manual Unoccupied 
1 Manual Occupied 
5  Manual Fan Only 
9 Manual Off 
255 Auto 






