Data Sheet for Product

Table Of Contents
Point Map
November, 2009
Siemens Industry, Inc. Page 1 of 2
Systems Integration
Trane Standard BACnet Points: CGA/CGW Scroll Chiller
Type Description Range/Units
LAI Leaving Chilled Water Temperature
°F
LAI Return Chilled Water Temperature
°F
LAI Condenser Refrigerant Temperature – Circuit 1
°F
LAI Condenser Refrigerant Temperature – Circuit 2
°F
LDI Chiller Status Off/On
LDI Chilled Water Flow Status No/Yes
LDI Manual Reset Alarm Off/On
LDI Ice Making Status Off/On
LDI Scroll Chiller Communications Fault/OK
LDO Chiller Enable Off/On
LDO Ice Making Enable Off/On
LDO Capacity Control Normal/Reduced
LAO Chilled Water Setpoint
°F
LAO Ice Making Termination Setpoint
°F
Additional points may be made available. Contact your local Trane representative for more information.