Data Sheet for Product

Table Of Contents
Point Map
November, 2009
Siemens Industry, Inc. Page 1 of 2
Systems Integration
Trane Standard BACnet Points: European Chiller (TEC)
Type Description Range/Units
LAI Leaving Chilled Water Temperature
°F
LAI Return Chilled Water Temperature
°F
LAI Leaving Condenser Water Temperature
°F
LAI Return Condenser Water Temperature
°F
LAI Condenser Refrigerant Temperature – Circuit 1
°F
LAI Condenser Refrigerant Temperature – Circuit 2
°F
LAI Condenser Refrigerant Pressure – Circuit 1 psig
LAI Condenser Refrigerant Pressure – Circuit 2 psig
LDI Chiller Status Off/On
LDI Chilled Water Flow Status No/Yes
LDI Automatic Reset Alarm Off/On
LDI Manuel Reset Alarm Off/On
LDI TEC Communications Fault/OK
LDI Heat/Cool Mode Heat/Cool
LDO Chiller Enable Off/On
LDO Capacity Control Normal/Reduced
LDO Heat Pump Chiller Mode Cooling/Heating
LDO Low Noise Mode Normal/Low
LAO Chilled Water Setpoint
°F
LAO Hot Water Setpoint
°F
Additional points may be made available. Contact your local Trane representative for more information.