Data Sheet for Product

Table Of Contents
Point Map
November, 2009
Siemens Industry, Inc. Page 1 of 2
Systems Integration
Trane Standard BACnet Points: UCP1 CenTraVac
Series R Chiller
Type Description Range/Units
LAI Leaving Chilled Water Temperature
°F
LAI Entering Chilled Water Temperature
°F
LAI Leaving Condenser Water Temperature
°F
LAI Entering Condenser Water Temperature
°F
LAI Compressor Current Draw % RLA
LAI Condenser Refrigerant Pressure psig
LAI Compressor Discharge Refrigerant/Oil Temperature
°F
LAI Evaporator Refrigerant Temperature
°F
LAI Condenser Refrigerant Temperature
°F
LDI Chiller Status Off/On
LDI Condenser Water Flow Status No/Yes
LDI Chilled Water Flow Status No/Yes
LDI Manual Reset Alarm Off/On
LDI Auto Reset Alarm Off/On
LDI UCP1 Communications Fault/OK
LDO Chiller Enable Off/On
LAO Chilled Water Setpoint
°F
LAO Current Limit Setpoint % RLA
Additional points may be made available. Contact your local Trane representative for more information.