Data Sheet for Product

Point Map
February 7, 2007
Systems Integration
YORK ISN Enhanced Driver: YI Isoow Absorption
Chillers
Table 1. YI APOGEE Points, Application Number: 5857.
Point Type Description Range/Units
abc
1
LAO
Device Address
2 LAI Device Application
3
LAO
Logon Pass
word
4
LAO Open Password
5
LDI
Yorktalk Transla tor Communication Status Normal/Fail
8LDI
Device Com
munication Status
Normal/Fa
il
9LAI
Leaving Chilled Water Temperature Set Point °F
°C
10 LAI
Remote Load Limit Set Point %
11 LDI
Start/Stop Status Off/On
12 LAI
Leaving Chilled Water Temperature °F
°C
13 LAI
Entering Chilled Water Temperature °F
°C
14 LAI
Generato
r Shell Pressure
psig
kPa
15 LAI
Entering Condenser Water Temperature °F
°C
16 LAI
Leaving Condenser Water Temperature °F
°C
17 LAI Automatic Decrystallization Temperature
°F
°C
18 LAI
Refrigerant Temperature L eavi ng The Condenser °F
°C
19 LAI
Steam/Hot Water Supply Temperature °F
°C
20 LAI
Steam S upply Pressu re (Steam Units On ly)
psig
kPa
21 LAI
Steam/Hot Water Actuator Valve Position %
continued on next page...