Data Sheet for Product
Point Map
February 7, 2007
Systems Integration
YORK ISN Enhanced Driver: YK Centrifugal “Super
Chillers”
Table 1. YK APOGEE Points, Application Number: 5858.
Point Type Description Range/Units
abc
1
LAO
Device Address
–
2 LAI Device Application
–
3
LAO
Logon Password
–
4
LAO Open Password
–
5
LDI
Yorktalk Translator Communication Statu s Normal/Fail
8LDI
Device Commu nication Status Normal/Fail
9LAI
Leaving Chilled Water Temperature Set Point °F
°C
10 LAI
Remote Current Set P o int %
11 LDI
Start/Stop Status Off/On
12 LDI
Fixed/Variable Speed Se lect Fixed/Variable
13 LAI
Leaving Chilled Water Temperature °F
°C
14 LAI
Entering Chilled Water Temperature °F
°C
15 LAI Evaporator Pre ssure psig
kPa
16 LAI
Condenser Pressure
psig
kPa
17 LAI
Oil Differential Pressure
psig
kPa
18 LAI
Entering Condenser Water Tempera t ure °F
°C
19 LAI
Leaving Cond enser Water Temperature °F
°C
20 LAI
% Motor Current %
21 LAI
Phase A Current
A
22 LAI
Phase B Current
A
23 LAI
Phase C Current
A