Data Sheet for Product
Point Map
February 7, 2007
Systems Integration
YORK ISN Enhanced Driver: YP Paraflow Absorption
Chillers
Table 1. Y P A POGEE Points, Application Number: 5859.
Point Type Description Range/Units
abc
1
LAO
Device Address
–
2 LAI Device Application
–
3
LAO
Logon Password
–
4
LAO Open Password
–
5
LDI
Yorktalk Translator Communication Statu s Normal/Fail
8LDI
Device Commu nication Statu s Normal/Fail
9LAI
Leaving Chilled Water Temperature Set Point °F
°C
10 LAI
Hot Water Temperature Set Point °F
°C
11 LAI
Remote Load Limit Set Poin t %
12 LDI
Start/Stop Status Off/On
13 LAI
Leaving Chilled Water Temperature °F
°C
14 LAI
Entering Chilled Water Temperature °F
°C
15 LAI
First Generator 1 Pressure
psig
kPa
16 LAI
First Generator 1 Tempe rature °F
°C
17 LAI
First Generator 2 Pressure
psig
kPa
18 LAI
Entering Condenser Water Tempera t ure °F
°C
19 LAI
Leaving Cond enser Water Temperature °F
°C
20 LAI
First Generator 2 Tempe rature °F
°C
21 LAI Leaving Hot Water Temperature
°F
°C