Siemens Data Sheet 6306
Smart Infrastructure - Building Products usa.siemens.com/fire
Intelligent Initiating Devices
HMS-Series
Models HMS-D I HMS-S I HMS-DZ I HMS-SZ
Architect & Engineer Specifications
Durable metal design
Shock and vibration resistant
Single-action (Model HMS-S | -SZ) and
double-action (Model HMS-D | -DZ)
stations
Pull-down lever is down, until
manually reset
▪ Reset with Allen Key
▪ No break rods necessary
Custom microcomputer-chip
technology
Polarity insensitive via SureWireTM
technology
Dynamic supervision to the fire-
alarm control panel (FACP)
▪ Device Programmer Unit
(Model DPU) programs and
verifies address and tests
functionality of each device
Electronic-address programming
(EEPROM) is easier, as well as more
efficient, dependable
Surface or semi-flush installation
Two-wire
Americans with Disabilities Act (ADA)
Compliant
UL Listed;
USCG (161.002/60/0),
FM (#3015946 & 3052621),
CSFM (#7150-0067:0036) and
NYC Fire Dept. (#202-12E, Vol. 1)
Approved
Product Overview
The Siemens intelligent manual fire-alarm boxes (Models HMS-S | HMS-SZ and
HMS-D | HMS-DZ) provide the most advanced method of address programming and
supervision.
Each Model HMS-series manual box achieves the state of an ‘intelligent-initiating
device’ by incorporating custom microcomputer-chip technology with sophisticated,
bi-directional communication capabilities with the panel, which include Siemens
Modular, as well as Siemens 50-point, 252-point and 504-point addressable FACPs.
The Model HMS- series manual fire-alarm boxes are also included in US Coast Guard
(USCG) approval for use in marine and other harsh environments, when used with
the Siemens 252-point and 504-point USCG approved addressable system.
Specifications
Models HMS-S | HMS-SZ and HMS-D | HMS-DZ are
constructed of durable, molded polycarbonate
material that is matte finished in red with raised
white lettering. The housing accommodates a ‘pull-
down’ lever, which ─ when operated ─ locks into
position; indicating the fire-alarm box has been
activated.
The pull-down lever remains down / in the ‘locked’
position, until the fire-alarm box is manually reset.
The manual fire alarm box can only be reset by
opening the hinged housing cover with an Allen key;
followed by closing and locking the cover. Models
HMS-S | -SZ and HMS-D | -DZ operate with Siemens ─
Fire Safety FACPs. The microcomputer chip to the
manual fire-alarm box has the capacity of storing ─
in memory ─ identification and important operating-
status data.
Models HMS-S | -SZ and HMS-D | -DZ are fitted with
screw terminals for connection to an addressable
circuit, and can be either surface or semi-flush
mounted.
The Model HMS-series manual fire-alarm boxes
derive their power, communicate information and
receive commands over a single pair of wires. Each
box is compatible on the same circuit with all Model
`H’-series detectors, interfaces or addressable,
conventional zone modules.
Model HMS-D | -DZ
Dual-Action Station
Model HMS-S | -SZ
Single-Action Station