Data Sheet for Product
2
Siemens Schweiz AG
A6V101107822_en--_f
Building Products
2021-01-13
Use
This product must only be used with Sinorix
TM
fixed automatic extinguishing systems.
Functions
MANOCAB range
The MANOCAB-START connection cable can be used to connect the first contact pressure
gauge electrically.
The MANOCAB-EXT cable is an extension cable, and available in lengths of 1.5 m and 5 m.
The MANOCAB-EXT extension cable can be connected to any point in the monitoring line,
e.g.
● between the MANOCAB-START connection cable and the first contact pressure gauge
on the line; or
● between two contact pressure gauges far apart, e.g. for the switch from row 2 to row 3
(rack change) for a battery of 140 l cylinders.
MANOEOL range
The MANOEOL end-of-line device terminates the monitoring line with a resistor which meets
the requirements of ECP X100 or XC10.
MANO-AH testing tool
The MANO-AH testing tool is used to simulate a "Loss of agent" signal. It ensures safety for
the technician during commissioning and maintenance activities.
Type summary
MANOCAB range
MANOCAB-START
Item
Description
Item
Description
1
Bare cable (brown, blue and black wires)
3
3-wire cable
2