User's Manual

Siemens PLT 112 · 2002
7/13
Migration of existing systems
Configuring lists
Migratable TELEPERM M modules in AS 488/TM
*) in certain circumstances there are some special features for these
modules, please ask your Siemens contact
Designation Order No.
of module
Release Remarks
Binary calculation modules
Binary calculation module
6DS1 717-8AA *) 8
SW:08
16) 24)
Binary/analog calculation
module (max. 31 channels)
6DS1 717-8RR 1
SW:3
16) 24)
Binary extension
6DS1 719-8AA 2 15)
Analog extension
6DS1 720-8AA 1 15)
Binary extension (for
6DS1 717-8RR)
6DS1 719-8RR 1
Coupling modules
S5-110A, with 4 channels
6DS1 310-8AA *) 8
S5-110A, with 1 channel 6DS1 310-8AB *) 8
S5 coupling, serial 6DS1 318-8AB *) 3
SW: 1
1) 24)
S5 coupling (expansion unit)
6DS1 321-8AA *) 4
S5 coupling, serial 6DS1 333-8AB *) 1
S7 coupling, serial 6DS1 333-8AB *) 1 22) 24)
MODBUS coupling
(on request)
6DS1 333-8AB *)
with M1328-V5
1
SW=5
3) 24)
I/O bus remote coupling
AS - I/O bus - ES 100 K
6DS1 322-8AA 5 1) 12)
S5 coupling, serial,
ET 100, EU / I/Os,
TM-S5 coupling module
6DS1 327-8AA *) 4
Coupling of external com-
puter via CS 275 / N-V.24
6DS1 202-8AB *) 5 19) 20)
CP 581 TM interface modules
CP 581 TM communications
module
6DS1 337-1AD *)
with S5KE, S5KS
1
SW: ...
2) 19)
20) 21)
CP 581 TM-L2 (DP/FDL)
6DS1 341-1AD *)
with S5KE, S5KS
1
SW: ...
2) 19)
20) 21)
CP 581 TM FUZZY
6DS1 342-1BD *)
with S5KE, S5KS
1
SW: ...
2) 19)
20) 21)
23) 24)
Explanations for the column „Remarks“
1) Earlier release versions not permissible!
2) Special product
3) Not a standard product, no system test carried out
5) Application only without interrupt!
6) No application as common alarm module (SF 61)
7) Approved for common alarm modules, the latest product release is
required.
8) Note current balance of subrack:
max. 4 A per module, max. 16 A per subrack
9) Combination modules for use in TELEPERM M standard systems
and in TELEPERM ME systems. Application in AS 235/488 extension
units only as TELEPERM ME module with slot addressing.
11) Note: Release 3 is not allowed!
12) Cycle time in TPM 478 for processing of modules in ES 100 K can
be delayed (dependent on the cable length); coupling modules are
used at best in the basic unit.
13) Application in ES 100 K not allowed (timing)
14) Connection of transmitters with two-wire system not permissible with
AS 488 K and ES 100 K in AC 230 V! The ripple of the power supply
in the AS is too high for these transmitters and the connection sys-
tem.
15) Module only functions together with 6DS1 717-8AA
16) Only alarm function
17) Module only functions together with 6DS1 713 or 6DS1 731.
19) A maximum of 1 module of type Typ N-V.24 or CP 581 TM are per-
missible in a AS 488/TM system (in basic and extension cabinet)
20) Application in ES 100 K not allowed (5 V power)
21) Hardware/software releases on request:
Siemens Karlsruhe,
I&S IT PS KHE3,
D-76181 Karlsruhe, Germany
22) S7 coupling with 3964 R / RK 512 procedure,
SEND/RECEIVE, SIMATIC S5 analog value format
23) only CP 581/TM versions with S5Kx drivers can be used. Power
balance of the module can vary up to max. 3 A (with +5 V)
24) cycle time of the process image min. 1 s
Explanations for the column „Release“
5 recommended minimum release (for technical reasons). With ear-
lier releases it’s possible to have some loss of functions and pro-
blems with I/Os; use without guarantee
1; 2; permissible releases
=5 valid release of a module
6 and remark 1) mean an imperative minimum release
(6 in this case), i.e. upgrading is essential at least up to release 6.
Observe the respective indexed remarks for the individual modules.
Observe the details described in the manual „Supplementary System
Documentation AS 388/TM and AS 488/TM“ (Chapter 6).