Operating instructions
3 Commissioning Issue B1
MICROMASTER 420 Operating Instructions
42 6SE6400-5AA00-0BP0
Flow chart Quick Commissioning (Level 1 Only)
1)
Motor-specific parameters – see motor rating plate.
2)
The parameters offer more setting options than listed here. See Parameter List for further setting
options.
P0010 Start Quick Commissioning
0 Ready to Run
1 Quick Commissioning
30 Factory Setting
Note
P0010 must always be set back to '0' before operating
the motor. However if P3900 = 1 is set after
commissioning this is done automatically.
P0100 Operation for Europe/N. America
0 Power in kW; f default 50 Hz
1 Power in hp; f default 60 Hz
2 Power in kW; f default 60 Hz
Note
Settings 0 & 1 should be changed using the DIP
switches to allow permanent setting.
P0305 Rated Motor Current
1)
0 - 2 x inverter rated current (A)
Nominal motor current (A) from rating plate
P0307 Rated Motor Power
1)
0 kW - 2000 kW
Nominal motor power (kW) from rating plate.
If P0100 = 1, values will be in hp
P0310 Rated Motor Frequenc
y
1)
12 Hz - 650 Hz
Nominal motor frequency (Hz) from rating plate
P0700 Selection of Command Source
2)
(on / off / reverse)
0 Factory Setting
1 Basic Operator Panel
2 Terminal / Digital Inputs
P1000 Selection of Frequency Setpoint
2)
0 No frequency setpoint
1 BOP frequency control ↑↓
2 Analogue Setpoint
P1080 Min. Motor Frequenc
y
Sets minimum motor frequency (0-650Hz) at which the
motor will run irrespective of the frequency setpoint.
The value set here is valid for both clockwise and anti-
clockwise rotation.
P1082 Max. Motor Frequenc
y
Sets maximum motor frequency (0-650Hz) at which
the motor will run at irrespective of the frequency
setpoint. The value set here is valid for both clockwise
and anti-clockwise rotation.
P1120 Ramp-Up Time
0 s - 650 s
Time taken for the motor to accelerate from standstill
up to maximum motor frequency.
P1121 Ramp-Down Time
0 s - 650 s
Time taken for motor to decelerate from maximum
motor frequency down to standstill.
P3900 End Quick Commissioning
0 End Quick Commissioning without motor
calculation or factory reset.
1 End Quick Commissioning with motor calculation
and factory reset (Recommended)
2 End Quick Commissioning with motor calculation
and with I/O reset.
3 End Quick Commissioning with motor calculation
but without I/O reset.
P0304 Rated Motor Voltage
1)
10 V - 2000 V
Nominal motor voltage (V) from rating plate
P0311 Rated Motor Speed
1)
0 - 40000 1/min
Nominal motor speed (rpm) from rating plate