Operating instructions
Issue B1 3 Commissioning
MICROMASTER 420 Operating Instructions
6SE6400-5AA00-0BP0
43
Motor data for parameterization
Figure 3-7 Typical Motor Rating Plate Example
NOTICE
♦ P0308 & P0309 are only visible if P0003 ≥ 2. Only one of the parameters are
shown depending on the settings of P0100.
♦ P0307 indicates kW or HP depending upon the setting of P0100. For detailed
information, please see the Parameter List.
♦ Changing motor parameters is not possible unless P0010=1.
♦ Ensure that the inverter is configured correctly to the motor, i.e. in the above
example delta terminal connection is for 230 V.
3.2.3.2 Reset to Factory default
To reset all parameters to the factory default settings; the following parameters
should be set as follows (BOP, AOP or Communication Option needed):
1. Set P0010 = 30
2. Set P0970 = 1
NOTE
The reset process can take up to 3 minutes to complete.