Operating instructions

5 System parameters Issue B1
MICROMASTER 420 Operating Instructions
66 6SE6400-5AA00-0BP0
PI Controller (P0004 = 22)
Par. No. Parametername Default Acc WS QC
P2200[1] BI: Enable PID controller 0:0 2 CT -
P2201 Fixed PID setpoint 1 0.00 2 CUT -
P2202 Fixed PID setpoint 2 10.00 2 CUT -
P2203 Fixed PID setpoint 3 20.00 2 CUT -
P2204 Fixed PID setpoint 4 30.00 2 CUT -
P2205 Fixed PID setpoint 5 40.00 2 CUT -
P2206 Fixed PID setpoint 6 50.00 2 CUT -
P2207 Fixed PID setpoint 7 60.00 2 CUT -
P2216 Fixed PID setpoint mode - Bit 0 1 3 CT -
P2217 Fixed PID setpoint mode - Bit 1 1 3 CT -
P2218 Fixed PID setpoint mode - Bit 2 1 3 CT -
r2224 CO: Act. fixed PID setpoint - 2 - -
P2231[1] Setpoint memory of PID-MOP 0 2 CUT -
P2232 Inhibit rev. direct. of PID-MOP 1 2 CT -
P2240[1] Setpoint of PID-MOP 10.00 2 CUT -
r2250 CO: Output setpoint of PID-MOP - 2 - -
P2253[1] CI: PID setpoint 0:0 2 CUT -
P2254[1] CI: PID trim source 0:0 3 CUT -
P2255 PID setpoint gain factor 100.00 3 CUT -
P2256 PID trim gain factor 100.00 3 CUT -
P2257 Ramp-up time for PID setpoint 1.00 2 CUT -
P2258 Ramp-down time for PID setpoint 1.00 2 CUT -
r2260 CO: Act. PID setpoint - 2 - -
P2261 PID setpoint filter timeconstant 0.00 3 CUT -
r2262 CO: Act. PID filtered setpoint - 3 - -
P2264[1] CI: PID feedback 755:0 2 CUT -
P2265 PID feedback filter timeconstant 0.00 2 CUT -
r2266 CO: PID feedback - 2 - -
P2267 Max. value for PID feedback 100.00 3 CUT -
P2268 Min. value for PID feedback 0.00 3 CUT -
P2269 Gain applied to PID feedback 100.00 3 CUT -
P2270[1] PID feedback function selector 0 3 CUT -
P2271 PID tranducer type 0 2 CUT -
r2272 CO: PID scaled feedback - 2 - -
r2273 CO: PID error - 2 - -
P2280 PID proportional gain 3.000 2 CUT -
P2285 PID integral time 0.000 2 CUT -
P2291 PID output upper limit 100.00 2 CUT -
P2292 PID output lower limit 0.00 2 CUT -
P2293 Ramp-up /-down time of PID limit 1.00 3 CUT -
r2294 CO: Act. PID output - 2 - -