Operating instructions

International English 5. SYSTEM PARAMETERS
80 MICROMASTER 420 Operating Instructions
6SE6400-5AA00-0BP0
Parameter
Number
Parameter Name
Min
Max
[Default]
Units
P0003 User
Access Level
P0004 Setting
Changeable
Status
P1311 Acceleration boost
Applies boost following a positive setpoint change and drops back out once the setpoint is
reached. This can be useful to improve response to small positive setpoint changes.
V
V Nom
(P0304)
100%
F Nom
(P0310)
F Max
(P1082)
Vmax
N
o
r
m
a
l
V
/
f
50%
F Boost Min
(P1305 - expert)
Vmax
Note
Increasing the Boost Levels increases the heating of the motor.
Refer to note in P1310 with respect to Boost priorities.
The achievable boost value is limited by the setting in P0640.
Σ Boosts < 300/I
mot
* R
S
0
250
[0]
%
2
13
Starting boostP1312
Applies a constant linear offset to the active V/f curve (either linear or quadratic) after an
ON command and is active until setpoint is reached for the 1
st
time. This is useful for
starting loads with high inertia.
V
V Nom
(P0304)
P1312
0
F Nom
(P0310)
F Max
(P1082)
V Max
V Max
Normal V/f
0
250
[0]
%
2
13