Operating instructions
04/02 1 Parameters
MICROMASTER 420 Parameter List
6SE6400-5BA00-0BP0
103
r2224 CO: Act. fixed PID setpoint
Min: -
Datatype: Float Unit: % Def: -
P-Group: TECH Max: -
Displays total output of PID fixed setpoint selection.
Note:
r2224 = 100 % corresponds to 4000 hex
P2231 Setpoint memory of PID-MOP Min: 0
CStat: CUT Datatype: U16 Unit: - Def: 0
P-Group: TECH Active: Immediately QuickComm. No Max: 1
Setpoint memory
Possible Settings:
0 PID-MOP setpoint will not be stored
1 PID-MOP setpoint will be stored (P2240 is updated)
Dependency:
P2231 = 0:
If 0 selected, setpoint returns to value set in P2240 (setpoint of PID-MOP) after an OFF command.
P2231 = 1:
If 1 is selected, active setpoint is 'remembered' and P2240 updated with current value.
Details:
See P2240 (setpoint of PID-MOP)
P2232 Inhibit rev. direct. of PID-MOP Min: 0
CStat: CT Datatype: U16 Unit: - Def: 1
P-Group: TECH Active: first confirm QuickComm. No Max: 1
Inhibits reverse setpoint selection when PID motor potentiometer is chosen either as a main setpoint or
additional setpoint.
Possible Settings:
0 Reverse direction is allowed
1 Reverse direction inhibited
Note:
Setting 0 enables a change of motor direction using the motor potentiometer setpoint (increase/decrease
frequency either by using digital inputs or motor potentiometer up/down buttons.
P2235 BI: Enable PID-MOP (UP-cmd) Min: 0:0
CStat: CT Datatype: U32 Unit: - Def: 19:13
P-Group: COMMANDS Active: first confirm QuickComm. No Max: 4000:0
Defines source of UP command.
Common Settings:
722.0 = Digital input 1 (requires P0701 to be set to 99, BICO)
722.1 = Digital input 2 (requires P0702 to be set to 99, BICO)
722.2 = Digital input 3 (requires P0703 to be set to 99, BICO)
19.D = Keypad UP cursor
Dependency:
To change setpoint:
1. Use UP / DOWN key on BOP or
2. Set P0702/P0703 = 13/14 (function of digital inputs 2 and 3)
P2236 BI: Enable PID-MOP (DOWN-cmd) Min: 0:0
CStat: CT Datatype: U32 Unit: - Def: 19:14
P-Group: COMMANDS Active: first confirm QuickComm. No Max: 4000:0
Defines source of DOWN command.
Common Settings:
722.0 = Digital input 1 (requires P0701 to be set to 99, BICO)
722.1 = Digital input 2 (requires P0702 to be set to 99, BICO)
722.2 = Digital input 3 (requires P0703 to be set to 99, BICO)
722.3 = Digital input 4 (via analog input, requires P0704 to be set to 99)
19.E = Keypad DOWN cursor
Dependency:
To change setpoint:
1. Use UP / DOWN key on BOP or
2. Set P0702/P0703 = 13/14 (function of digital inputs 2 and 3)
P2240 Setpoint of PID-MOP Min: -130.00
CStat: CUT Datatype: Float Unit: % Def: 10.00
P-Group: TECH Active: Immediately QuickComm. No Max: 130.00
Setpoint of the motor potentiometer.
Allows user to set a digital PID setpoint in [%].
Note:
P2240 = 100 % corresponds to 4000 hex
Level:
2
Level:
2
Level:
2
Level:
3
Level:
3
Level:
2