MM420 Parameter List 04/02
MICROMASTER 420 Parameter List
110 6SE6400-5BA00-0BP0
P3980 Commissioning command selection Min: 0
CStat: T Datatype: U16 Unit: - Def: 0
P-Group: - Active: first confirm QuickComm. No Max: 66
Toggles command and setpoint sources between freely programmable BICO parameters and fixed
command/setpoint profiles for commissioning.
The command and setpoint sources can be changed independently. The tens digit selects the command
source, the ones digit the setpoint source.
Possible Settings:
0 Cmd = BICO parameter Setpoint = BICO parameter
1 Cmd = BICO parameter Setpoint = MOP setpoint
2 Cmd = BICO parameter Setpoint = Analog setpoint
3 Cmd = BICO parameter Setpoint = Fixed frequency
4 Cmd = BICO parameter Setpoint = USS on BOP link
5 Cmd = BICO parameter Setpoint = USS on COM link
6 Cmd = BICO parameter Setpoint = CB on COM link
10 Cmd = BOP Setpoint = BICO parameter
11 Cmd = BOP Setpoint = MOP setpoint
12 Cmd = BOP Setpoint = Analog setpoint
13 Cmd = BOP Setpoint = Fixed frequency
15 Cmd = BOP Setpoint = USS on COM link
16 Cmd = BOP Setpoint = CB on COM link
40 Cmd = USS on BOP link Setpoint = BICO parameter
41 Cmd = USS on BOP link Setpoint = MOP setpoint
42 Cmd = USS on BOP link Setpoint = Analog setpoint
43 Cmd = USS on BOP link Setpoint = Fixed frequency
44 Cmd = USS on BOP link Setpoint = USS on BOP link
45 Cmd = USS on BOP link Setpoint = USS on COM link
46 Cmd = USS on BOP link Setpoint = CB on COM link
50 Cmd = USS on COM link Setpoint = BICO parameter
51 Cmd = USS on COM link Setpoint = MOP setpoint
52 Cmd = USS on COM link Setpoint = Analog setpoint
53 Cmd = USS on COM link Setpoint = Fixed frequency
54 Cmd = USS on COM link Setpoint = USS on BOP link
55 Cmd = USS on COM link Setpoint = USS on COM link
60 Cmd = CB on COM link Setpoint = BICO parameter
61 Cmd = CB on COM link Setpoint = MOP setpoint
62 Cmd = CB on COM link Setpoint = Analog setpoint
63 Cmd = CB on COM link Setpoint = Fixed frequency
64 Cmd = CB on COM link Setpoint = USS on BOP link
66 Cmd = CB on COM link Setpoint = CB on COM link
P3981 Reset active fault Min: 0
CStat: CT Datatype: U16 Unit: - Def: 0
P-Group: ALARMS Active: first confirm QuickComm. No Max: 1
Resets active faults when changed from 0 to 1.
Possible Settings:
0 No fault reset
1 Reset fault
Note:
Automatically reset to 0.
Details:
See P0947 (last fault code)
Level:
4