MM420 Parameter List 04/02
MICROMASTER 420 Parameter List
16 6SE6400-5BA00-0BP0
r0052 CO/BO: Act. status word 1 Min: -
Datatype: U16 Unit: - Def: -
P-Group: COMMANDS Max: -
Displays first active status word of inverter (bit format) and can be used to diagnose inverter status. The
display segments for the status word are shown in the "Introduction to MICROMASTER System
Parameters".
Bitfields:
Bit00 Drive ready 0 NO
1 YES
Bit01 Drive ready to run 0 NO
1 YES
Bit02 Drive running 0 NO
1 YES
Bit03 Drive fault active 0 NO
1 YES
Bit04 OFF2 active 0 YES
1NO
Bit05 OFF3 active 0 YES
1NO
Bit06 ON inhibit active 0 NO
1 YES
Bit07 Drive warning active 0 NO
1 YES
Bit08 Deviation setpoint / act. value 0 YES
1NO
Bit09 PZD control 0 NO
1 YES
Bit10 Maximum frequency reached 0 NO
1 YES
Bit11 Warning: Motor current limit 0 YES
1NO
Bit12 Motor holding brake active 0 NO
1 YES
Bit13 Motor overload 0 YES
1NO
Bit14 Motor runs right 0 NO
1 YES
Bit15 Inverter overload 0 YES
1NO
Note:
Output of Bit3 (Fault) will be inverted on digital output (Low = Fault, High = No Fault).
Level:
2