P0753 Smooth time ADC Min: 0
CStat: CUT Datatype: U16 Unit: ms Def: 3
P-Group: TERMINAL Active: first confirm QuickComm. No Max: 10000
Defines filter time (PT1 filter) in [ms] for analog input.
Note:
Increasing this time (smooth) reduces jitter but slows down response to the analog input.
P0753 = 0 : No filtering
r0754 Act. ADC value after scaling [%] Min: -
Datatype: Float Unit: % Def: -
P-Group: TERMINAL Max: -
Shows smoothed value of analog input in [%] after scaling block.
Dependency:
P0757 to P0760 define range (ADC scaling).
r0755 CO: Act. ADC after scal. [4000h] Min: -
Datatype: I16 Unit: - Def: -
P-Group: TERMINAL Max: -
Displays analog input, scaled using ASPmin and ASPmax.
Analog setpoint (ASP) from the analog scaling block can vary from min. analog setpoint (ASPmin) to a max.
analog setpoint (ASPmax) as shown in P0757 (ADC scaling).
The largest magnitude (value without sign) of ASPmin and ASPmax defines the scaling of 16384.
Example:
ASPmin = 300 %, ASPmax = 100 % then 16384 represents 300 %.
This parameter will vary from 5461 to 16384
ASPmin = -200 %, ASPmax = 100 % then 16384 represents 200 %.
This parameter will vary from -16384 to +8192
Note:
This value is used as an input to analog BICO connectors.
ASPmax represents the highest analog setpoint (this may be at 10 V).
ASPmin represents the lowest analog setpoint (this may be at 0 V).
Details:
See parameters P0757 to P0760 (ADC scaling)
P0756 Type of ADC Min: 0
CStat: CT Datatype: U16 Unit: - Def: 0
P-Group: TERMINAL Active: first confirm QuickComm. No Max: 1
Defines type of analog input and also enables analog input monitoring.
Possible Settings:
0 Unipolar voltage input (0 to +10 V)
1 Unipolar voltage input with monitoring (0 to 10 V)
Dependency:
Function disabled if analog scaling block programmed to output negative setpoints (see P0757 to P0760).
Notice:
When monitoring is enabled and a deadband defined (P0761), a fault condition will be generated (F0080) if
the analog input voltage falls below 50 % of the deadband voltage.
Details:
See P0757 to P0760 (ADC scaling).