Operating instructions

04/02 1 Parameters
MICROMASTER 420 Parameter List
6SE6400-5BA00-0BP0
87
P2016[4] CI: PZD to BOP link (USS)
Min: 0:0
CStat: CT Datatype: U32 Unit: - Def: 52:0
P-Group: COMM Active: Immediately QuickComm. No Max: 4000:0
Selects signals to be transmitted to serial interface via BOP link.
STXLGEADRBCC
USS telegram
P2012
Parameter
Process data
PKWPZD
PZD mapping from parameter P2016
PZD1
ZSW1
PZD2
HIW
PZD3PZD4
ZSW2
USS on BOP link
[0]
P2016
[1]
[2]
[3]
STX
LGE
ADR
Start of text
Length
Address
PKW
PZD
BCC
Parameter ID value
Process data
Block check character
ZSW
HIW
Status word
Main actual value
r0021
r0052
r0052
r0053
r0053
Index:
P2016[0] : Transmitted word 0
P2016[1] : Transmitted word 1
P2016[2] : Transmitted word 2
P2016[3] : Transmitted word 3
Example:
P2016[0] = 52.0 (default). In this case, the value of r0052[0] (CO/BO: Status word) is transmitted as 1st
PZD to the BOP link.
Note:
If r0052 not indexed, display does not show an index (".0" ).
r2018[4] CO: PZD from COM link (USS) Min: -
Datatype: U16 Unit: - Def: -
P-Group: COMM Max: -
Displays process data received via USS on COM link.
STX
LGE
ADR
Start of text
Length
Address
PKW
PZD
BCC
Parameter ID value
Process data
Block check character
PZD mapping to parameter r2018
r2037
r2036
STW
HSW
Control word
Main setpoint
USS on COM link
[0]
r2018
[1]
[2]
[3]
STXLGEADRBCC
PZD1
STW1
PZD2
HSW
PZD3PZD4
STW2
USS telegram
P2012
Parameter
Process data
PKWPZD
Index:
r2018[0] : Received word 0
r2018[1] : Received word 1
r2018[2] : Received word 2
r2018[3] : Received word 3
Note:
The control words can be viewed as bit parameters r2036 and r2037.
Level:
3
Level:
3