Installation Guide

4099823 Rev.B
CATALOG NUMBER:
MM0404L1400RLM
FOR OVERHEAD AND UNDERGROUND
SERVICE SURFACE MOUNT
: CIRCUIT MAY BE LIVE WITH
METER REMOVED.
DEVICE RATING:
400 AMPS MAXIMUM; 120/240 V ~(4 JAW) OR
208Y/120 V ~ (5 JAW); SINGLE PHASE, THREE
WIRE.
METER SOCKET: 4 JAW; LEVER OPERATED
BYPASS WITH JAW TENSION RELEASE.
RATING: 400 AMPS (320 AMPS CONTINUOUS)
SUITABLE ONLY FOR USE AS SERVICE
EQUIPMENT.
CAUTION
Outdoor Combination Metering
ENCLOSURE
TYPE 3R
S
TERMINAL TIGHTENING TORQUES LB.-IN.:
kcmil OR AWG
WIRE SIZE
600 - 500 kcmil 500 _ _ _
500 - 350 kcmil 500 _ _ 450
350kcmil-3/0 500 250 _ 450
2/0 _ 250 50 _
1/0-#6 _ 250 50 _
TERMINAL RANGES, kcmil OR AWG:
= LIMITED TO (1)600kcmil-#4
OR (2)350kcmil-1/0
= (1)#250kcmil-6
= (1)2/0-#12
= LIMITED TO (1) 500kcmil-3/0
OR (2) 250kcmil-3/0
HARDWARE TIGHTENING TORQUES:
3/8 NUTS ........ 250-350 IN.-LBS.
ACCESSORIES
FILLER PLATE QF3
5TH JAW SHIELD S35815-2
FOR HUB, ORDER FROM “HD”
SERIES
COVERPLATE HD000
3” HUB HD300
3 ½”HUB HD350
4”HUB Hd400
EQUIPMENT
GROUND
NEUTRAL
(BONDED)
NEUTRAL
BARRIER