Installation Instructions and Wiring for
CAT. NO. FDLC - Faraday Device Loop Card
INTRODUCTION: The Faraday Device Loop Card (FDLC) is the driver for the Faraday X1 Addressable
smoke detectors, manual stations, monitor devices and control devices used on the MPC-6000 and MPC-
7000 Fire Alarm System Control Units. The FDLC contains 9 LEDs for diagnosis of problems.
OPERATION: The FDLC initializes, operates, and maintains all devices residing on the loop. The FDLC
communicates all relevant device and event information, such as alarms and troubles, to the Main System
Board. The sensitivity of any intelligent smoke detector and the logic functions of any intelligent output
devices can be checked and adjusted from the system display and keypad. All information about the
devices on the loop can be displayed on the system display. The FDLC allows the system polarity
insensitive devices to be connected without generating errors.
The FDLC supports one loop of 252 Faraday X1 intelligent field devices (252 addresses) as well as device
accessories (relay bases, audible bases, and remote lamps) in any combination. (The on-board
microprocessor provides the FDLC with the ability to function and initiate alarm conditions even if the main
board microprocessor fails.)
The FDLC contains one reset switch, and 9 LEDs as shown in Figure 1. Pushing the RESET switch (S1)
re-initializes the FDLC operation.