Installation Instructions

Air Duct Monitoring Housing
Installation Instructions
Model 8744
INTRODUCTION Model 8744 from Faraday is an air duct monitoring housing
containing sampling tubes. When used with a 8854 smoke
detector, smoke and combustion products are detected for
shutdown of the duct system and/or operation of supple-
mentary equipment as provided by the system control panel.
The duct unit supports two sets of Form C alarm contacts,
one Form A alarm contact and one Form C trouble contact.
The trouble contact supervises the presence of the input
power, removal of the detector cover and the removal of the
smoke detector head.
TECHNICAL DATA AIR DUCT CONDITIONS
Temperature Range:
32
O
F (0
O
C) - 100
O
F (38
O
C) per UL 268A
Altitude Range:
No altitude limitations
Relative Humidity:
Up to 85% RH (non-condensing/non-freezing)
Air Duct Velocity Range:
100-4000 ft/min
Sampling and Exhaust Tube Pressure Differential Range:
Greater than 0.01 and less than 1.2 inches of water column
These air duct detectors are designed for detection and
control of products of combustion in a duct system.
They areThey are
They areThey are
They are
not to be used as a substnot to be used as a subst
not to be used as a substnot to be used as a subst
not to be used as a subst
itit
itit
it
utut
utut
ut
ion forion for
ion forion for
ion for
open area prot open area prot
open area prot open area prot
open area prot
ectect
ectect
ect
ion.ion.
ion.ion.
ion.
DO NOT USE air duct detectors with Alarm Verification.
ASSEMBLY This detector has a cover tamper (removal) switch. Care
should be taken when installing the cover. Squarely place the
cover on the unit to aviod possible damage to the switch.
DO NOT SLIDE COVER INTO POSITION.
Siemens Industry, Inc.
Building Technologies Division Florham Park, NJ
Tel: (973) 593-2600 Fax: (973) 593-6670
Web: www.faradayfirealarms.com
P/N 315-049709FA-3