Installation Instructions
Siemens Building Technologies, Inc.
8 Fernwood Road
Florham Park, New Jersey 07932
P/N 315-049590FA-1
INSTALLATION INSTRUCTIONS FOR
CAT. NO. RPT-1 RELEASING TRANSFORMER
The RPT-1 Releasing Transformer is for the MPC-REL Releasing Module of the MPC-6000 Fire
Alarm Control Unit. The RPT-1 provides 3.0 Amps of current to the MPC-REL Releasing Module
of the MPC-6000 Fire Alarm Control Unit. The RPT-1 mounts above the standard NPE-1
transformer(s).
PARTS SUPPLIED
1 RPT-1 Releasing Transformer
2 899-G67197 Keps Nuts - #6-32
1 315-049590FA Instruction Sheet
1.) Installation is to be done by qualified
personnel who have thoroughly read
and understood this instruction sheet.
2.) Disconnect BATTERY and AC prior to
working on equipment.
3.) Place the RPT-1 releasing transformer
assembly over the upper pair of studs
on the left side of the enclosure.
4.) Tighten transformer-mounting nuts
(P/N 899-G67197).
5.) Plug the transformer assembly 6-pin
connector to J3 on the Main
Termination Board and 2-pin
connector to J3 of MPC-REL.
6.) Apply power to system.
7.) Check for proper operation.
8.) Refer to the MPC-6000/-7000/RND-2
Installation, Operation and
Maintenance Manual, P/N 315-
447309, for more information
RPT-1
Releasing
Transformer
Keps Nut (2)
#6-32
Existing
NPE-1
Transformers