Installation Instructions
P/N 315-095302-7
Figure 1
MSI-B6F Cover
OPERATION
The MSI-B6F manual stations operate with the MXL
Control Panel.
When an alarm condition occurs, pull down on the
PULL DOWN lever of the manual station. The pull-
down cover remains down and locked until the station
is reset.
The MSI-B6F with the MS-FD Adapter has an addi-
tional lever labeled LIFT - PULL HANDLE which must
be lifted up before access is provided to the station
PULL DOWN lever.
TO RESET STATION
1. Turn lock barrel 1/4 turn counter-clockwise with
the allen key provided. This will allow the front to
hinge down, releasing PULL-DOWN plate to
disengage from the switch.
2. Return the front to its closed position, then turn
the lock barrel back clockwise.
WIRING
Wire the station to the System (Refer to Figure 2 for
proper connections.) All wiring must comply with
national and local codes.
INTRODUCTION
The Manual Station Model MSI-B6F from Siemens
Industry, Inc., is an addressable device containing
advanced control panel communication technology.
This technology which provides bidirectional commu-
nication with the control panel, produces an Intelligent
Initiating Device. The MSI-B6F is a single action
station; when used with the MS-FD Adapter, the
MSI-B6F is a double action station.
PROGRAMMING
IMPORTANT NOTE
The MSI-B6F must be in the Reset position in
order for the unit to be programmed. If the pull-
down lever has been even partially pulled down,
the unit must be reset before it can be programmed.
1. Refer to Figure 1 to locate the opening on the
MSI-B6F cover that allows access to the
programming holes which are on the MSI-B6F
printed circuit board.
2. The manual station is programmed by using
either the FPI-32 Programmer Tester or the DPU
Programmer/Tester.
Note: The connection for the FPI-32 Programmer
to the manual station is not polarity sensitive.
However, connection from the Control Panel to
the MSI-B6F is polarity sensitive.
3. Follow the instructions given in the FPI-32
Programmer/Tester Manual (P/N 315-090077) or
the DPU User's Manual (P/N 315-033260), as
applicable, to connect the cable provided and
program the MSI-B6F to the desired address.
4. Record the device address on the nameplate
located on the inside of the manual station
mounting plate.
5. The MSI-B6F can now be installed and wired to
the system.
Siemens Industry, Inc.
Building Technologies Division
Florham Park, NJ
Siemens Building Technologies, Ltd.
Fire Safety & Security Products
2 Kenview Boulevard
Brampton, Ontario
L6T 5E4 Canada
Installation Instructions
MODEL MSI-B6F
Metal Manual Station