Installation Instructions
P/N 315-095302-7
NOTES:
1. Recommended wire sizes:
18 AWG minimum, 14 AWG maximum
2. Wire larger than 14 AWG can damage the connector.
3. When using shielded cable without metal raceway or with
nonmetallic raceway, the shields should be terminated at the
device box and the device ground terminal. If the device box is
already grounded by another means, such as being mounted to
a grounded structure, the wire shields should be continuous and
must be grounded solely at the point of origin; for example, at
the control panel.
4. When using shielded cable with metal raceway, the wiring
shields shall be continuous and grounded solely at the point of
origin. The device ground terminal shall be connected to the
grounded device box.
5. When using metal raceway without shielded cable, connect
the device ground terminal to the grounded device box.
6. Metal raceway should be thoroughly grounded throughout the
system.
+
+
_
_
TO NEXT ADDRESSABLE DEVICE
EARTH GROUND
1
2
3
FROM INITIATING MXL CONTROL PANEL
OR PREVIOUS ADDRESSABLE DEVICE
INSTALLATION
1. Distribute the manual station boxes throughout
the protected area so that they are unobstructed,
readily accessible, and located in the normal exit
path.
2. Place the manual station according to the
regulations of the authorities having jurisdiction.
For surface mounting, mount the station to a
Model MS-FB Backbox as shown in Figure 3.
Figure 3
Surface Mounting the MSI-B6F
Figure 2
Wiring the MSI-B6F
Figure 4
Flush Munting the MSI-B6F
For flush mounting, mount the station to a user-
supplied single gang switchbox 3-1/2" deep. See
Figure 4.
CAUTION: Do not overtighten the screws.
Overtightening may distort the backplate.
3. Wire the station to the System (Refer to Figure 2
for proper connections).