User Manual

GAMMA instabus
Technical Product-Information
July 2020
Power Supply Unit N 125/02 5WG1125-1AB02
Power Supply Unit N 125/12 5WG1125-1AB12
Power Supply Unit N 125/22 5WG1125-1AB22
2 / 4
Siemens Schweiz AG
Smart Infrastructure
Global Headquarters
Theilerstrasse 1a
CH 6300 Zug
RS-AA
© Siemens AG 2020
Subject to change
Update: http://www.siemens.com/gamma-td
Installation Instructions
The device may be used for permanent interior installa-
tions in dry locations within distribution boards or
small casings with DIN rail EN 60715-TH35.
WARNUNG
The device may be built into distribution boards
(230/400 V) together only with appropriate VDE-de-
vices.
The device must be mounted and commissioned by an
authorised electrician.
A safety disconnection of the device must be possible.
The prevailing safety rules must be heeded.
The device must not be opened.
For planning and construction of electric installations,
the relevant guidelines, regulations and standards of
the respective country are to be considered.
Technical Data
Input voltage
rated voltage: AC 120-230 V, 50...60 Hz
DC 220 V
permissible range: AC 102...253V, DC 176...270 V
Rated power intake
approx. 24 VA
Output voltage
rated voltage: DC 24 V
safety extra low voltage (SELV)
permissible range: DC 21...30 V
Output current
rated current 160 mA (N 125/02),
320 mA (N 125/12),
640 mA (N 125/22)
short-circuit current:
limited to
1.0 A (N 125/02, N 125/12),
1.5 A (N 125/22)
Backup interval
on input voltage failure: approx. 200 ms at rated current
Operator elements
slide switch: for resetting the bus devices connected to
the line (operation > 20 s)
Display elements
1 red LED: for indicating a voltage interruption on
operating the slide switch in RESET-position
1 green LED: for indicating normal operation
1 red LED: for indicating a shorted-out bus line or
device over-load
Connections
mains connection, screwless plug-in terminals:
strip insulation for 10...11 mm
permissible conductor types/cross sections:
- 0.5...3.3 mm² ( AWG 12) single core
- 0.5...1.5 mm² plain flexible conductor
- 0.5...3.3 mm² (AWG 12) stranded conductor
- 0.5...3.3 mm² (AWG 12) flexible conductor with ter-
minal pin, crimped on gas tight