User Manual

2 Parameters
2.2 List of parameters
SINAMICS G120 CU230P-2 Control Units
110 List Manual (LH9), 04/2014, A5E33838102B AA
Re bit 05:
A data set changeover is only carried out when pole position identification is not running.
Re bit 07:
A data set changeover is only carried out when rotating measurement is not running.
Re bit 08:
A data set changeover is only carried out when motor data identification is not running.
Description: Displays the command data set (CDS) selected via the binector input.
Dependency: Refer to: r0050, p0810, p0811
Note: Command data sets are selected via binector input p0810 and following.
The currently effective command data set is displayed in r0050.
Description: Displays the drive data set (DDS) selected via the binector input.
Dependency: Refer to: r0051, p0820, p0821
Note: Drive data sets are selected via binector input p0820 and following.
The currently effective drive data set is displayed in r0051.
If there is only one data set, then a value of 0 is displayed in this parameter and not the selection via binector inputs.
Description: Sets the signal source for the command "ON/OFF (OFF1)".
For the PROFIdrive profile, this command corresponds to control word 1 bit 0 (STW1.0).
Recommend.: When the setting for this binector input is changed, the motor can only be switched on by means of an appropriate
signal change of the source.
Dependency: Refer to: p1055, p1056
Caution: When "master control from PC" is activated, this binector input is ineffective.
r0836.0...1 CO/BO: Command Data Set CDS selected / CDS selected
Access level: 3 Calculated: - Data type: Unsigned8
Can be changed: - Scaling: - Dyn. index: -
Units group: - Unit selection: - Func. diagram: 8560
Min Max Factory setting
- - -
Bit field: Bit Signal name 1 signal 0 signal FP
00 CDS select. bit 0 ON OFF -
01 CDS select. bit 1 ON OFF -
r0837.0...1 CO/BO: Drive Data Set DDS selected / DDS selected
Access level: 3 Calculated: - Data type: Unsigned8
Can be changed: - Scaling: - Dyn. index: -
Units group: - Unit selection: - Func. diagram: 8565
Min Max Factory setting
- - -
Bit field: Bit Signal name 1 signal 0 signal FP
00 DDS select. bit 0 ON OFF -
01 DDS select. bit 1 ON OFF -
p0840[0...n] BI: ON / OFF (OFF1) / ON / OFF (OFF1)
CU230P-2_BT
CU230P-2_CAN
CU230P-2_HVAC
Access level: 3 Calculated: - Data type: U32 / Binary
Can be changed: T Scaling: - Dyn. index: CDS, p0170
Units group: - Unit selection: - Func. diagram: 2501, 2610, 8720,
8820, 8920
Min Max Factory setting
- - [0] 722.0
[1] 0
[2] 0
[3] 0