User Manual

SINAMICS G120 CU230P-2 Control Units
List Manual (LH9), 04/2014, A5E33838102B AA
201
2 Parameters
2.2 List of parameters
Description: Controlled reluctance motor:
Sets the lower flux limit to evaluate the optimum flux characteristic p2970ff.
The value is referred to the rated motor flux (p0357 * r0331).
Description: Sets the smoothing time for the flux setpoint.
Description: Sets the smoothing time for the flux setpoint in the field-weakening range
Recommend.: Smoothing should be especially used if there is no regenerative feedback into the line supply. This means that the
DC link voltage can quickly increase in regenerative operation
Note: Only the flux setpoint rise is smoothed
Description: Sets the scaling of the pre-control characteristic for the start of field weakening.
For values above 100 % and for partial load situations, the field weakening starts at higher speeds.
Note: If the start of field weakening is shifted to lower speeds, then the voltage reserve is increased for partial load
situations.
If the start of field weakening is shifted to higher speeds, the voltage reserve is appropriately reduced so that for fast
load changes, it can be expected that this will have a negative impact on the dynamic performance.
Description: Sets the proportional gain for the flux controller.
Note: The value is automatically pre-assigned dependent on the motor when the drive system is first commissioned.
When calculating controller parameters (p0340 = 4), this value is re-calculated.
p1581[0...n] Flux reduction factor / Flux red factor
Access level: 3 Calculated: - Data type: FloatingPoint32
Can be changed: U, T Scaling: - Dyn. index: DDS, p0180
Units group: - Unit selection: - Func. diagram: -
Min Max Factory setting
0 [%] 100 [%] 100 [%]
p1582[0...n] Flux setpoint smoothing time / Flux setp T_smth
Access level: 3 Calculated: p0340 = 1,3 Data type: FloatingPoint32
Can be changed: U, T Scaling: - Dyn. index: DDS, p0180
Units group: - Unit selection: - Func. diagram: 6722, 6724
Min Max Factory setting
4 [ms] 5000 [ms] 15 [ms]
p1584[0...n] Field weakening operation flux setpoint smoothing time / Field weak T_smth
Access level: 4 Calculated: p0340 = 1,3 Data type: FloatingPoint32
Can be changed: U, T Scaling: - Dyn. index: DDS, p0180
Units group: - Unit selection: - Func. diagram: 6722
Min Max Factory setting
0 [ms] 20000 [ms] 0 [ms]
p1586[0...n] Field weakening characteristic scaling / Field weak scal
Access level: 4 Calculated: - Data type: FloatingPoint32
Can be changed: U, T Scaling: - Dyn. index: DDS, p0180
Units group: - Unit selection: - Func. diagram: -
Min Max Factory setting
80.0 [%] 120.0 [%] 100.0 [%]
p1590[0...n] Flux controller P gain / Flux controller Kp
Access level: 4 Calculated: p0340 = 1,3,4 Data type: FloatingPoint32
Can be changed: U, T Scaling: - Dyn. index: DDS, p0180
Units group: - Unit selection: - Func. diagram: 6723
Min Max Factory setting
0.0 999999.0 10.0