2 Parameters
2.2 List of parameters
Description: Displays the P component of the controller for speed adaptation.
Description: Displays the I component of the controller for speed adaptation.
Description: Sets the offset voltage in the alpha direction; this compensates the offset voltages of the drive converter/inverter at
low speeds. The value is valid for the rated (nominal) pulse frequency of the power unit.
Note: The value is pre-set during the rotating measurement.
Description: Sets the offset voltage in the beta direction; this compensates the offset voltages of the drive converter/inverter at low
speeds. The value is valid for the rated (nominal) pulse frequency of the power unit.
Note: The value is pre-set during the rotating measurement.
Description: Displays the internal status signals of the motor model:
Index 0: Changeover ramp between current and voltage models
Index 1: Changeover ramp for model tracking (encoderless induction motors only)
Index 2: Changeover ramp for zero frequency range (encoderless induction motors only)
Index: [0] = Changeover ramp motor model
[1] = Changeover ramp model tracking
[2] = Changeover ramp zero frequency encoderless ASM
[3...6] = Reserved
r1770 CO: Motor model speed adaptation proportional component / MotMod n_adapt Kp
Access level: 4 Calculated: - Data type: FloatingPoint32
Can be changed: - Scaling: p2000 Dyn. index: -
Units group: 3_1 Unit selection: p0505 Func. diagram: 6730
Min Max Factory setting
- [rpm] - [rpm] - [rpm]
r1771 CO: Motor model speed adaptation I comp. / MotMod n_adapt Tn
Access level: 4 Calculated: - Data type: FloatingPoint32
Can be changed: - Scaling: p2000 Dyn. index: -
Units group: 3_1 Unit selection: p0505 Func. diagram: 6730
Min Max Factory setting
- [rpm] - [rpm] - [rpm]
p1774[0...n] Motor model offset voltage compensation alpha / MotMod offs comp A
Access level: 4 Calculated: - Data type: FloatingPoint32
Can be changed: U, T Scaling: - Dyn. index: DDS, p0180
Units group: - Unit selection: - Func. diagram: -
Min Max Factory setting
-5.000 [V] 5.000 [V] 0.000 [V]
p1775[0...n] Motor model offset voltage compensation beta / MotMod offs comp B
Access level: 4 Calculated: - Data type: FloatingPoint32
Can be changed: U, T Scaling: - Dyn. index: DDS, p0180
Units group: - Unit selection: - Func. diagram: -
Min Max Factory setting
-5.000 [V] 5.000 [V] 0.000 [V]
r1776[0...6] Motor model status signals / MotMod status sig
Access level: 4 Calculated: - Data type: FloatingPoint32
Can be changed: - Scaling: - Dyn. index: -
Units group: - Unit selection: - Func. diagram: -
Min Max Factory setting
- - -