User Manual

2 Parameters
2.2 List of parameters
SINAMICS G120 CU230P-2 Control Units
218 List Manual (LH9), 04/2014, A5E33838102B AA
Dependency: If a sine-wave filter is parameterized as output filter (p0230 = 3, 4), then only space vector modulation without
overcontrol can be selected as modulation type (p1802 = 3). This does not apply to power units PM260.
p1802 = 10 can only be set for power units PM230 and PM240 and for r0204.15 = 0.
Refer to: p0500
Notice: When modulation modes are enabled that could lead to overmodulation (p1802 = 0, 2), the modulation depth must be
limited using p1803 (default p1803 < 100 %). The higher the overmodulation, the greater the current ripple and
torque ripple.
When changing p1802[x], the values for all of the other existing indices are also changed.
Note: The setting p1802 = 19 is only released for chassis power units and SIMOTICS FD motors.
Description: Defines the maximum modulation depth.
Dependency: Refer to: p0500
Note: p1803 = 100% is the overcontrol limit for space vector modulation (for an ideal drive converter without any switching
delay).
Description: Defines the maximum modulation depth.
Dependency: Refer to: p0500
Note: p1803 = 100% is the overcontrol limit for space vector modulation (for an ideal drive converter without any switching
delay).
Description: Defines the maximum modulation depth.
Dependency: Default setting PM260: 103 %.
Refer to: p0500
Note: p1803 = 100% is the overcontrol limit for space vector modulation (for an ideal drive converter without any switching
delay).
Description: Defines the maximum modulation depth.
Dependency: Refer to: p0500
Note: p1803 = 100% is the overcontrol limit for space vector modulation (for an ideal drive converter without any switching
delay).
p1803[0...n] Maximum modulation depth / Modulat depth max
PM230 Access level: 4 Calculated: p0340 = 1,3,5 Data type: FloatingPoint32
Can be changed: U, T Scaling: - Dyn. index: DDS, p0180
Units group: - Unit selection: - Func. diagram: 6723
Min Max Factory setting
20.0 [%] 120.0 [%] 115.0 [%]
p1803[0...n] Maximum modulation depth / Modulat depth max
PM240 Access level: 3 Calculated: p0340 = 1,3,5 Data type: FloatingPoint32
Can be changed: U, T Scaling: - Dyn. index: DDS, p0180
Units group: - Unit selection: - Func. diagram: 6723
Min Max Factory setting
20.0 [%] 150.0 [%] 106.0 [%]
p1803[0...n] Maximum modulation depth / Modulat depth max
PM250
PM260
Access level: 3 Calculated: p0340 = 1,3,5 Data type: FloatingPoint32
Can be changed: U, T Scaling: - Dyn. index: DDS, p0180
Units group: - Unit selection: - Func. diagram: 6723
Min Max Factory setting
20.0 [%] 150.0 [%] 106.0 [%]
p1803[0...n] Maximum modulation depth / Modulat depth max
PM330 Access level: 4 Calculated: p0340 = 1,3,5 Data type: FloatingPoint32
Can be changed: U, T Scaling: - Dyn. index: DDS, p0180
Units group: - Unit selection: - Func. diagram: 6723
Min Max Factory setting
20.0 [%] 150.0 [%] 106.0 [%]