2 Parameters
2.2 List of parameters
Description: Sets the configuration for the test pulse evaluation.
Bit 00: Check for conductor-to-conductor short circuit once/always when the pulses are enabled.
Bit 01: Check for ground fault once/always when the pulses are enabled.
Bit 02: Activation of the tests selected using bit 00 and/or bit 01 each time the pulses are enabled
Dependency: Refer to: p0287
Note: If a conductor-to-conductor short-circuit is detected during the test, this is displayed in r1902.1.
If a ground fault is detected during the test, this is displayed in r1902.2.
Re bit 02 = 0:
If the test was successful once after POWER ON (see r1902.0), it is not repeated.
Re bit 02 = 1:
The test is not only performed after POWER ON, but also each time the pulses are enabled.
Description: Sets the configuration for the test pulse evaluation.
Bit 00: Check for conductor-to-conductor short circuit once/always when the pulses are enabled.
Bit 01: Check for ground fault once/always when the pulses are enabled.
Bit 02: Activation of the tests selected using bit 00 and/or bit 01 each time the pulses are enabled
Dependency: Refer to: p0287
Note: If a conductor-to-conductor short-circuit is detected during the test, this is displayed in r1902.1.
If a ground fault is detected during the test, this is displayed in r1902.2.
Re bit 02 = 0:
If the test was successful once after POWER ON (see r1902.0), it is not repeated.
Re bit 02 = 1:
The test is not only performed after POWER ON, but also each time the pulses are enabled.
For chassis power units, the ground fault is also determined using the summed output current (see p0287).
Description: Displays the status of the test pulse evaluation.
p1901 Test pulse evaluation configuration / Test puls config
PM230
PM240
PM250, PM260
Access level: 3 Calculated: p0340 = 1 Data type: Unsigned32
Can be changed: T Scaling: - Dyn. index: -
Units group: - Unit selection: - Func. diagram: -
Min Max Factory setting
- - 0000 bin
Bit field: Bit Signal name 1 signal 0 signal FP
00 Phase short-circuit test pulse active Yes No -
01 Ground fault detection test pulse active Yes No -
02 Test pulse at each pulse enable Yes No -
p1901 Test pulse evaluation configuration / Test puls config
PM330 Access level: 3 Calculated: p0340 = 1 Data type: Unsigned32
Can be changed: T Scaling: - Dyn. index: -
Units group: - Unit selection: - Func. diagram: -
Min Max Factory setting
- - 0000 bin
Bit field: Bit Signal name 1 signal 0 signal FP
00 Phase short-circuit test pulse active Yes No -
01 Ground fault detection test pulse active Yes No -
02 Test pulse at each pulse enable Yes No -
r1902 Test pulse evaluation status / Test puls ev stat
Access level: 4 Calculated: - Data type: Unsigned32
Can be changed: - Scaling: - Dyn. index: -
Units group: - Unit selection: - Func. diagram: -
Min Max Factory setting
- - -