SINAMICS G120 CU230P-2 Control Units
262 List Manual (LH9), 04/2014, A5E33838102B AA
Description: Sets the second signal source to acknowledge faults.
Note: A fault acknowledgement is triggered with a 0/1 signal.
Description: Sets the third signal source to acknowledge faults.
Note: A fault acknowledgement is triggered with a 0/1 signal.
Description: Sets the signal source for external fault 1.
Note: An external fault is triggered with a 1/0 signal.
Description: Sets the signal source for external fault 2.
Note: An external fault is triggered with a 1/0 signal.
Description: Sets the signal source for external fault 3.
External fault 3 is initiated by the following AND logic operation:
- BI: p2108 negated
- BI: p3111
- BI: p3112 negated
Dependency: Refer to: p3110, p3111, p3112
Note: An external fault is triggered with a 1/0 signal.
p2104[0...n] BI: 2. Acknowledge faults / 2. Acknowledge
CU230P-2_DP
CU230P-2_PN
Access level: 3 Calculated: - Data type: U32 / Binary
Can be changed: U, T Scaling: - Dyn. index: CDS, p0170
Units group: - Unit selection: - Func. diagram: 2546, 8060
Min Max Factory setting
- - [0] 722.2
[1] 0
[2] 0
[3] 0
p2105[0...n] BI: 3. Acknowledge faults / 3. Acknowledge
Access level: 3 Calculated: - Data type: U32 / Binary
Can be changed: U, T Scaling: - Dyn. index: CDS, p0170
Units group: - Unit selection: - Func. diagram: 2546, 8060
Min Max Factory setting
- - 0
p2106[0...n] BI: External fault 1 / External fault 1
Access level: 3 Calculated: - Data type: U32 / Binary
Can be changed: U, T Scaling: - Dyn. index: CDS, p0170
Units group: - Unit selection: - Func. diagram: 2546
Min Max Factory setting
- - 1
p2107[0...n] BI: External fault 2 / External fault 2
Access level: 3 Calculated: - Data type: U32 / Binary
Can be changed: U, T Scaling: - Dyn. index: CDS, p0170
Units group: - Unit selection: - Func. diagram: 2546
Min Max Factory setting
- - 1
p2108[0...n] BI: External fault 3 / External fault 3
PM230
PM240
PM250, PM260
Access level: 3 Calculated: - Data type: U32 / Binary
Can be changed: U, T Scaling: - Dyn. index: CDS, p0170
Units group: - Unit selection: - Func. diagram: 2546
Min Max Factory setting
- - 1