2 Parameters
2.2 List of parameters
Description: Sets the signal source for the setpoint for p3881 = 4 (technology controller) in the essential service mode (ESM).
Dependency: Refer to: p3881
Note: ESM: Essential Service Mode
Re p3884 = 0:
The technology controller uses the setpoint from p2253.
Description: Displays the number of activations and faults that have occurred for the essential service mode (ESM).
Index: [0] = Activation of the essential service mode
[1] = Faults during the essential service mode
Dependency: Refer to: p3888
Note: ESM: Essential Service Mode
Description: Setting to reset the number of activations and faults that have occurred for the essential service mode (ESM).
1: counter reset active (r3887[0, 1])
0: inactive
Dependency: Refer to: r3887
Note: ESM: Essential Service Mode
The parameter is automatically reset to zero after the counter has been reset.
Description: Display and BICO output for the status word of the essential service mode (ESM).
p3884 CI: ESM setpoint technology controller / ESM setp tech_ctrl
Access level: 3 Calculated: - Data type: U32 / FloatingPoint32
Can be changed: U, T Scaling: PERCENT Dyn. index: -
Units group: - Unit selection: - Func. diagram: 7033
Min Max Factory setting
- - 0
r3887[0...1] ESM number of activations/faults / ESM act/fault qty
Access level: 4 Calculated: - Data type: Unsigned16
Can be changed: - Scaling: - Dyn. index: -
Units group: - Unit selection: - Func. diagram: 7033
Min Max Factory setting
- - -
p3888 ESM reset number of activations/faults / ESM act/F qty r
Access level: 4 Calculated: - Data type: Unsigned8
Can be changed: T Scaling: - Dyn. index: -
Units group: - Unit selection: - Func. diagram: 7033
Min Max Factory setting
0 1 0
r3889.0...10 CO/BO: ESM status word / ESM ZSW
Access level: 3 Calculated: - Data type: Unsigned32
Can be changed: - Scaling: - Dyn. index: -
Units group: - Unit selection: - Func. diagram: 7033
Min Max Factory setting
- - -
Bit field: Bit Signal name 1 signal 0 signal FP
00 Essential service mode (ESM) activated Yes No -
01 Direction of rotation inverted Yes No -
02 Setpoint signal lost Yes No -
03 Technology controller actual value (p2264)
lost
Yes No -
04 Bypass active Yes No -
05 Setpoint technology controller
parameterized (p3884)
Yes No -