User Manual

2 Parameters
2.2 List of parameters
SINAMICS G120 CU230P-2 Control Units
346 List Manual (LH9), 04/2014, A5E33838102B AA
Description: Displays the Pre-defined Error Field of the CAN node.
It includes the number of all errors that have occurred, the number of errors that have occurred for each drive and the
errors according to their history.
The first 16 bits represent the CANopen error code and the second 16 bits the SINAMICS error code.
Index 1 has the same structure - however, the drive object ID is in the second 16 bits instead of the SINAMICS error
code.
CANopen error code:
0000 hex: No error present.
8110 hex: Alarm A08751 present.
8120 hex: Alarm A08752 present.
8130 hex: Alarm A08700(F) with alarm value = 2 present.
1000 hex: Generic error 1 present (there is at least one fault outside the range 8700 ... 8799)
1001 hex: Generic error 2 present (there is at least one alarm in the range 8700 ... 8799 with the exception of
A08751, A08752, A08700)
All drive objects are acknowledged by writing the value 0 to index 0. As soon as a fault has been acknowledged or an
alarm cleared, then it is also cleared from the fault list.
Index: [0] = Number of all faults in the drive unit
[1] = Most recent drive number / fault number
[2] = Number of faults drive 1
[3] = Fault 1/ drive 1
[4] = Fault 2/ drive 1
[5] = Fault 3/ drive 1
[6] = Fault 4/ drive 1
[7] = Fault 5/ drive 1
[8] = Fault 6/ drive 1
Note: Corresponds to the CANopen object 1003 hex.
Description: Display or setting of the CANopen Node ID.
The Node ID can be set as follows:
1) Using the address switch on the Control Unit.
--> p8620 can then only be read and displays the selected Node ID.
--> A change only becomes effective after a POWER ON.
--> CANopen Node ID and PROFIBUS address are identical.
2) Using p8620
--> Only if address 0 is set using the address switch.
--> the Node ID is set as standard to 126.
--> A change only becomes effective after save and POWER ON.
Dependency: Refer to: r8621
Notice: For p0014 = 1, the following applies:
After the value has been modified, no further parameter modifications can be made and the status is shown in r3996.
Modifications can be made again when r3996 = 0.
p8611[0...82] CAN Pre-defined Error Field / Pre_def err field
CU230P-2_CAN Access level: 3 Calculated: - Data type: Unsigned32
Can be changed: U, T Scaling: - Dyn. index: -
Units group: - Unit selection: - Func. diagram: -
Min Max Factory setting
0000 hex FFFF 1000 hex 0000 hex
p8620 CAN Node-ID / Node ID
CU230P-2_CAN Access level: 2 Calculated: - Data type: Unsigned8
Can be changed: T Scaling: - Dyn. index: -
Units group: - Unit selection: - Func. diagram: -
Min Max Factory setting
1 127 126