2 Parameters
2.2 List of parameters
SINAMICS G120 CU230P-2 Control Units
386 List Manual (LH9), 04/2014, A5E33838102B AA
Description: Sets the integral time (I component, integrating time constant) of the free technology controller 0.
Note: Value = 0: The integral time is disabled.
If the parameter is set to zero during operation, the I component retains its most recent value.
Description: Sets the maximum limit of the free technology controller 0.
Dependency: Refer to: p11092
Note: The maximum limit must always be greater than the minimum limit (p11091 > p11092).
Description: Sets the minimum limit of the free technology controller 0.
Dependency: Refer to: p11091
Note: The maximum limit must always be greater than the minimum limit (p11091 > p11092).
Description: Sets the ramp-up and ramp-down time for the maximum and minimum limit (p11091, p11092) of the free technology
controller 0.
Dependency: Refer to: p11091, p11092
Note: The ramp-up/ramp-down times are referred to 100%.
Description: Display and connector output for the output signal of the free technology controller 0.
p11085 Free tec_ctrl 0 integral time / Ftec0 Tn
Access level: 2 Calculated: - Data type: FloatingPoint32
Can be changed: U, T Scaling: - Dyn. index: -
Units group: - Unit selection: - Func. diagram: 7030
Min Max Factory setting
0.000 [s] 10000.000 [s] 30.000 [s]
p11091 CO: Free tec_ctrl 0 limit maximum / Ftec0 lim max
Access level: 3 Calculated: - Data type: FloatingPoint32
Can be changed: U, T Scaling: PERCENT Dyn. index: -
Units group: - Unit selection: - Func. diagram: 7030
Min Max Factory setting
-200.00 [%] 200.00 [%] 100.00 [%]
p11092 CO: Free tec_ctrl 0 limit minimum / Ftec0 lim min
Access level: 3 Calculated: - Data type: FloatingPoint32
Can be changed: U, T Scaling: PERCENT Dyn. index: -
Units group: - Unit selection: - Func. diagram: 7030
Min Max Factory setting
-200.00 [%] 200.00 [%] 0.00 [%]
p11093 Free tec_ctrl 0 limit ramp-up/ramp-down time / Ftec0 lim r-u/r-dn
Access level: 3 Calculated: - Data type: FloatingPoint32
Can be changed: U, T Scaling: - Dyn. index: -
Units group: - Unit selection: - Func. diagram: 7030
Min Max Factory setting
0.00 [s] 100.00 [s] 1.00 [s]
r11094 CO: Free tec_ctrl 0 output signal / Ftec0 out_sig
Access level: 2 Calculated: - Data type: FloatingPoint32
Can be changed: - Scaling: PERCENT Dyn. index: -
Units group: - Unit selection: - Func. diagram: 7030
Min Max Factory setting
- [%] - [%] - [%]