User Manual

3 Function diagrams
3.8 Internal control/status words
SINAMICS G120 CU230P-2 Control Units
560 List Manual (LH9), 04/2014, A5E33838102B AA
Fig. 3-55 2536 – Status word, monitoring functions 2
- 2536 -
Function diagram
87654321
fp_2536_97_01.vsd
Internal control/status words
G120 CU230P-2
07.04.2014 V4.7
Status word, monitoring functions 2
11
12
13
14
15
9
10
8
6
5
4
3
2
1
0
7
From speed signals
From speed signals
From torque messages, motor locked/stalled
From torque messages, motor locked/stalled
From load monitoring
From load monitoring
Status word, monitoring functions 2 (r2198)Bit No.
1 = |I_act| < I_threshold p2170
Reserved
Reserved
1 = |n_set| < p2161
1 = n_set > 0
1 = Motor blocked
1 = Motor stalled
1 = Load monitoring signals an alarm
1 = Load monitoring signals a fault
ZSW monitor 2
r2198
r2198
From extended signals
r2198.4
r2198.5
r2198.11
r2198.12
r2198.6
r2198.7
r2198.8
[8011.8]
[8011.8]
[8012.7]
[8012.8]
[8013.8]
[8013.8]
[8020.8]
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
[2530.2]