User Manual

List of parameters
Parameters
1-105
© Siemens AG 2008 - 2013 All Rights Reserved
SINAMICS G120 CU230P-2 Control Units List Manual (LH9), 01/2013
Note: Procedure:
1. In Index 0, enter which drive data set is to be copied.
2. In Index 1, enter the drive data set data that is to be copied into.
3. Start copying: Set index 2 from 0 to 1.
p0819[2] is automatically set to 0 when copying is completed.
Description: Sets the signal source to select the Drive Data Set, bit 0 (DDS, bit 0).
Dependency: Refer to: r0051, p0826, r0837
Notice: The parameter may be protected as a result of p0922 or p2079 and cannot be changed.
Description: Sets the signal source to select the Drive Data Set, bit 1 (DDS, bit 1).
Dependency: Refer to: r0051, r0837
Notice: The parameter may be protected as a result of p0922 or p2079 and cannot be changed.
Description: Sets the freely-assignable motor number for the drive data set changeover.
If the same motor is driven by different drive data sets, the same motor number must also be entered in these data
sets.
If the motor is also switched with the drive data set, different motor numbers must be used. In this case, the data set
can only be switched when the pulse inhibit is set.
Note: If the motor numbers are identical, the same thermal motor model is used for calculation after data set changeover.
If different motor numbers are used, different models are also used for calculating (the inactive motor cools down in
each case).
For the same motor number, the correction values of the Rs, Lh or kT adaptation are applied for the data set
changeover (refer to r1782, r1787, r1797).
Description: Displays the status word for the drive data set changeover.
p0820[0...n] BI: Drive Data Set selection DDS bit 0 / DDS select bit 0
Access level: 3 Calculated: - Data type: U32 / Binary
Can be changed: C(15), T Scaling: - Dyn. index: CDS, p0170
Units group: - Unit selection: - Func. diagram: 8565, 8575
Min Max Factory setting
- - 0
p0821[0...n] BI: Drive Data Set selection DDS bit 1 / DDS select bit 1
Access level: 3 Calculated: - Data type: U32 / Binary
Can be changed: C(15), T Scaling: - Dyn. index: CDS, p0170
Units group: - Unit selection: - Func. diagram: 8565
Min Max Factory setting
- - 0
p0826[0...n] Motor changeover motor number / Mot_chng mot No.
Access level: 3 Calculated: - Data type: Unsigned16
Can be changed: C(3), T Scaling: - Dyn. index: MDS
Units group: - Unit selection: - Func. diagram: -
Min Max Factory setting
0 3 0
r0835.2...8 CO/BO: Data set changeover status word / DDS_ZSW
Access level: 2 Calculated: - Data type: Unsigned16
Can be changed: - Scaling: - Dyn. index: -
Units group: - Unit selection: - Func. diagram: 8575
Min Max Factory setting
- - -