User Manual

Parameters
List of parameters
1-138
© Siemens AG 2008 - 2013 All Rights Reserved
SINAMICS G120 CU230P-2 Control Units List Manual (LH9), 01/2013
Description: Sets the signal source for the main setpoint.
Examples:
r1024: Fixed speed setpoint effective
r1050: Motor. potentiometer setpoint after the ramp-function generator
Dependency: Refer to: p1071, r1073, r1078
Notice: The parameter may be protected as a result of p0922 or p2079 and cannot be changed.
Description: Sets the signal source for the main setpoint.
Examples:
r1024: Fixed speed setpoint effective
r1050: Motor. potentiometer setpoint after the ramp-function generator
Dependency: Refer to: p1071, r1073, r1078
Notice: The parameter may be protected as a result of p0922 or p2079 and cannot be changed.
Description: Sets the signal source for scaling the main setpoint.
Description: Displays the effective main setpoint.
The value shown is the main setpoint after scaling.
p1070[0...n] CI: Main setpoint / Main setpoint
CU230P-2_BT
CU230P-2_CAN
CU230P-2_HVAC
Access level: 3 Calculated: - Data type: U32 / FloatingPoint32
Can be changed: T Scaling: p2000 Dyn. index: CDS, p0170
Units group: - Unit selection: - Func. diagram: 1550, 3030
Min Max Factory setting
- - [0] 755[0]
[1] 0
[2] 0
[3] 0
p1070[0...n] CI: Main setpoint / Main setpoint
CU230P-2_DP
CU230P-2_PN
Access level: 3 Calculated: - Data type: U32 / FloatingPoint32
Can be changed: T Scaling: p2000 Dyn. index: CDS, p0170
Units group: - Unit selection: - Func. diagram: 1550, 3030
Min Max Factory setting
- - [0] 2050[1]
[1] 0
[2] 0
[3] 0
p1071[0...n] CI: Main setpoint scaling / Main setp scal
Access level: 3 Calculated: - Data type: U32 / FloatingPoint32
Can be changed: T Scaling: PERCENT Dyn. index: CDS, p0170
Units group: - Unit selection: - Func. diagram: 1550, 3030
Min Max Factory setting
- - 1
r1073 CO: Main setpoint effective / Main setpoint eff
Access level: 3 Calculated: - Data type: FloatingPoint32
Can be changed: - Scaling: p2000 Dyn. index: -
Units group: 3_1 Unit selection: p0505 Func. diagram: 3030
Min Max Factory setting
- [rpm] - [rpm] - [rpm]