User Manual

List of parameters
Parameters
1-275
© Siemens AG 2008 - 2013 All Rights Reserved
SINAMICS G120 CU230P-2 Control Units List Manual (LH9), 01/2013
Description: Sets the speed/torque envelope curve for load monitoring.
Dependency: The following applies: p2190 < p2189
Refer to: p2184, p2189
Note: The lower envelope curve is defined by p2186, p2188 and p2190.
Description: Sets the delay time to evaluate the load monitoring.
Description: Sets the load monitoring configuration.
Value: 0: Monitoring switched out
1: Monitoring torque and load drop
2: Monitoring speed and load drop
3: Monitoring load drop
Dependency: Refer to: p2182, p2183, p2184, p2185, p2186, p2187, p2188, p2189, p2190, p2192, r2198, p3230, p3231, p3232
Refer to: A07920, A07921, A07922, F07923, F07924, F07925, F07936
Description: Displays the first status word for monitoring functions.
p2190[0...n] Load monitoring torque threshold 3 lower / M_thresh 3 lower
Access level: 3 Calculated: - Data type: FloatingPoint32
Can be changed: U, T Scaling: - Dyn. index: DDS, p0180
Units group: 7_1 Unit selection: p0505 Func. diagram: 8013
Min Max Factory setting
0.00 [Nm] 20000000.00 [Nm] 0.00 [Nm]
p2192[0...n] Load monitoring delay time / Load monit t_del
Access level: 3 Calculated: - Data type: FloatingPoint32
Can be changed: U, T Scaling: - Dyn. index: DDS, p0180
Units group: - Unit selection: - Func. diagram: 8013
Min Max Factory setting
0.00 [s] 65.00 [s] 10.00 [s]
p2193[0...n] Load monitoring configuration / Load monit config
Access level: 3 Calculated: - Data type: Integer16
Can be changed: U, T Scaling: - Dyn. index: DDS, p0180
Units group: - Unit selection: - Func. diagram: 8013
Min Max Factory setting
0 3 1
r2197.0...13 CO/BO: Status word monitoring 1 / ZSW monitor 1
Access level: 3 Calculated: - Data type: Unsigned16
Can be changed: - Scaling: - Dyn. index: -
Units group: - Unit selection: - Func. diagram: 1530, 2534
Min Max Factory setting
- - -
Bit field: Bit Signal name 1 signal 0 signal FP
00 |n_act| <= n_min p1080 Yes No 8020
01 |n_act| <= speed threshold value 2 p2155 Yes No 8010
02 |n_act| > speed threshold value 2 p2155 Yes No 8010
03 n_act >= 0 Yes No 8011
04 |n_act| >= n_set Yes No 8020
05 |n_act| <= n_standstill p1226 Yes No 8020
06 |n_act| > n_max Yes No 8010
07 Speed setp - act val deviation in tolerance
t_off
Yes No 8011
08 I_act >= I_threshold value p2170 Yes No 8020
09 Vdc_act <= Vdc_threshold value p2172 Yes No 8020
10 Vdc_act > Vdc_threshold value p2172 Yes No 8020