Description: Sets the permissible speed deviation during load monitoring (for p2193 = 2).
Dependency: Refer to: r2169, p2181, p2193, p3230
Refer to: A07920, A07921, A07922, F07923, F07924, F07925
Description: Sets the signal source for detecting a failure.
Dependency: Refer to: p2192, p2193
Refer to: F07936
Note: Monitoring is triggered with a 0 signal, as soon as the time in p2192 has expired.
Description: Sets the time constant for the PT1 element to smooth the torque actual value.
The smoothed torque actual value is compared with the threshold values and is only used for messages and sig-
nals.
Description: Sets the monitoring time for phase failure detection of the motor.
Notice: After the value has been modified, no further parameter modifications can be made and the status is shown in
r3996. Modifications can be made again when r3996 = 0.
Note: For p3235 = 0 the function is deactivated.
The monitoring is automatically de-activated during the flying restart operation for a motor that is still rotating.
3-phase phase failures cannot be detected and are indicated by other messages (e.g. F07902).
p3231[0...n] Load monitoring speed deviation / Load monit n_dev
Access level: 3 Calculated: - Data type: FloatingPoint32
Can be changed: U, T Scaling: - Dyn. index: DDS, p0180
Units group: 3_1 Unit selection: p0505 Func. diagram: 8013
Min Max Factory setting
0.00 [rpm] 210000.00 [rpm] 150.00 [rpm]
p3232[0...n] BI: Load monitoring failure detection / Load_moni fail_det
Access level: 3 Calculated: - Data type: U32 / Binary
Can be changed: U, T Scaling: - Dyn. index: CDS, p0170
Units group: - Unit selection: - Func. diagram: 8013
Min Max Factory setting
- - 1
p3233[0...n] Torque actual value filter time constant / M_act_filt T
Access level: 3 Calculated: - Data type: FloatingPoint32
Can be changed: U, T Scaling: - Dyn. index: DDS, p0180
Units group: - Unit selection: - Func. diagram: 8013
Min Max Factory setting
0 [ms] 1000000 [ms] 100 [ms]
p3235 Phase failure signal motor monitoring time / Ph_fail t_monit
Access level: 4 Calculated: - Data type: FloatingPoint32
Can be changed: U, T Scaling: - Dyn. index: -
Units group: - Unit selection: - Func. diagram: -
Min Max Factory setting
0 [ms] 2000 [ms] 320 [ms]