User Manual

Parameters
List of parameters
1-90
© Siemens AG 2008 - 2013 All Rights Reserved
SINAMICS G120 CU230P-2 Control Units List Manual (LH9), 01/2013
Description: Displays the status of digital outputs.
Note: DO: Digital Output
T: Terminal
Relay output: NO = normally open, NC = normally closed
Inversion using p0748 has been taken into account.
Description: Setting to invert the signals at the digital outputs.
Note: DO: Digital Output
T: Terminal
Relay output: NO = normally open, NC = normally closed
Description: Displays the status of analog inputs.
Note: AI: Analog Input
r0747 CU digital outputs status / CU DO status
Access level: 3 Calculated: - Data type: Unsigned32
Can be changed: - Scaling: - Dyn. index: -
Units group: - Unit selection: - Func. diagram: 2130, 2131, 2132,
2133
Min Max Factory setting
- - -
Bit field: Bit Signal name 1 signal 0 signal FP
00 DO 0 (NO: T. 19 / NC: T. 18) High Low -
01 DO 1 (NO: T. 21) High Low -
02 DO 2 (NO: T. 24 / NC: T. 23) High Low -
p0748 CU invert digital outputs / CU DO inv
Access level: 3 Calculated: - Data type: Unsigned32
Can be changed: U, T Scaling: - Dyn. index: -
Units group: - Unit selection: - Func. diagram: 2030, 2031, 2130,
2131, 2132, 2133
Min Max Factory setting
- - 0000 bin
Bit field: Bit Signal name 1 signal 0 signal FP
00 DO 0 (NO: T. 19 / NC: T. 18) Inverted Not inverted -
01 DO 1 (NO: T. 21) Inverted Not inverted -
02 DO 2 (NO: T. 24 / NC: T. 23) Inverted Not inverted -
r0751.0...10 BO: CU analog inputs status word / CU AI status word
Access level: 3 Calculated: - Data type: Unsigned16
Can be changed: - Scaling: - Dyn. index: -
Units group: - Unit selection: - Func. diagram: 9566, 9568
Min Max Factory setting
- - -
Bit field: Bit Signal name 1 signal 0 signal FP
00 Analog input AI0 wire breakage Yes No -
01 Analog input AI1 wire breakage Yes No -
02 Analog input AI2 wire breakage Yes No -
08 Analog input AI0 no wire breakage Yes No -
09 Analog input AI1 no wire breakage Yes No -
10 Analog input AI2 no wire breakage Yes No -