User Manual

Parameters
Introduction to Parameters
1-12
© Siemens AG 2011 All Rights Reserved
SINAMICS G120 Control Units CU230P-2 Parameter Manual (LH9), 06/2011
Can be changed
Inverter state in which the parameter is changeable.
Three states are possible:
In these states the parameter can be changed. One, two or all three states may
be specified. If all three states are specified, it is possible to change the parameter
setting in all three inverter states. (x) shows, that the parameter is only change-
able when p0010 = x.
Data Set
Parameters which are dependent on a data set are identified as follows:
CDS (Command Data Set)
They are always indexed with [0 ... n] with n = 0 ... 3 depending on setting in
p0170.
[0] = Command Data Set 0
[1] = Command Data Set 1
etc.
DDS (Drive Data Set)
They are always indexed with [0 ... n] with n = 0 ... 3 depending on setting in
p0180.
[0] = Drive Data Set 0
[1] = Drive Data Set 1
etc.
MDS (Motor Data Set) and PDS (Power unit Data Set)
They are always indexed with [0 ... n] with n = 0 ... 3 depending on setting in
p0180. The Motor Data Sets and Power unit Data Sets are allocated to the Drive
Data Sets, i.e. they are automatically addressed with the selection of a Drive Data
Set (e.g. Drive Data Set 1 includes Motor Data Set 1 and Power unit Data Set 1).
Data sets can only be applied and cleared when p0010 = 15 is set.
Commissioning C(x)
Run U
Ready to run T