Description: Sets the signal source for the setpoint of the motorized potentiometer in the automatic mode.
Dependency: Refer to: p1041
Description: Sets the signal source to accept the setting value for the motorized potentiometer.
Dependency: Refer to: p1044
Note: The setting value (CI: p1044) becomes effective for a 0/1 edge of the setting command (BI: p1043).
Description: Sets the signal source for the setting value for the motorized potentiometer.
Dependency: Refer to: p1043
Note: The setting value (CI: p1044) becomes effective for a 0/1 edge of the setting command (BI: p1043).
Description: Sets the effective setpoint in front of the internal motorized potentiometer ramp-function generator.
Description: Sets the ramp-up time for the internal ramp-function generator for the motorized potentiometer.
The setpoint is changed from zero up to the speed/velocity limit (p1082) within this time (if no initial rounding-off has
been activated).
Dependency: Refer to: p1030, p1048, p1082
Note: When the initial rounding-off is activated (p1030.2) the ramp-up time is correspondingly extended.
p1042[0...n] CI: Motorized potentiometer automatic setpoint / Mop auto setpoint
Access level: 3 Calculated: - Data type: U32 / FloatingPoint32
Can be changed: T Scaling: p2000 Data set: CDS, p0170
Units group: - Unit selection: -
Min Max Factory setting
- - 0
p1043[0...n] BI: Motorized potentiometer accept setting value / MotP acc set val
Access level: 3 Calculated: - Data type: U32 / Binary
Can be changed: T Scaling: - Data set: CDS, p0170
Units group: - Unit selection: -
Min Max Factory setting
- - 0
p1044[0...n] CI: Motorized potentiometer setting value / Mop set val
Access level: 3 Calculated: - Data type: U32 / FloatingPoint32
Can be changed: T Scaling: p2000 Data set: CDS, p0170
Units group: - Unit selection: -
Min Max Factory setting
- - 0
r1045 CO: Mot. potentiometer speed setp. in front of ramp-fct. gen. / Mop n_set bef RFG
Access level: 3 Calculated: - Data type: FloatingPoint32
Can be changed: - Scaling: p2000 Data set: -
Units group: 3_1 Unit selection: p0505
Min Max Factory setting
- [rpm] - [rpm] - [rpm]
p1047[0...n] Motorized potentiometer ramp-up time / Mop ramp-up time
Access level: 2 Calculated: - Data type: FloatingPoint32
Can be changed: U, T Scaling: - Data set: DDS, p0180
Units group: - Unit selection: -
Min Max Factory setting
0.000 [s] 1000.000 [s] 10.000 [s]