List of Parameters
1-142
© Siemens AG 2011 All Rights Reserved
SINAMICS G120 Control Units CU230P-2 Parameter Manual (LH9), 06/2011
Description: Sets the signal source to select the total setpoint.
Dependency: The selection of the total speed setpoint is automatically interconnected to the status word of the technology con-
troller (r2349.4) if the technology controller is selected (p2200 > 0) and operated in the mode p2251 = 0.
If the hibernation function is activated (p2398 = 1), an interconnection is made to r2399.7.
Refer to: p1109
Caution: If the technology controller is to supply the total setpoint using p1109, then it is not permissible to disable the inter-
connection to its status word (r2349.4). If the hibernation function is activated, then it is not permissible to disable
the interconnection to status word r2399.
Description: Sets the signal source for the total setpoint.
For p1108 = 1 signal, the total setpoint is read in via p1109.
Dependency: The signal source of the total setpoint is automatically interconnected to the output of the technology controller
(r2294) if the technology controller is selected (p2200 > 0) and operated in the mode p2251 = 0.
If the hibernation function is activated (p2398 = 1), an interconnection is made to r2397[0].
Refer to: p1108
Caution: If the technology controller is to supply the total setpoint using p1109, then it is not permissible to disable the inter-
connection to its output (r2294).
If the hibernation function is activated, then it is not permissible to withdraw the interconnection to setpoint r2398[0].
Description: Sets the signal source to disable the negative direction.
Dependency: Refer to: p1111
Description: Sets the signal source to disable the positive direction.
Dependency: Refer to: p1110
p1108[0...n] BI: Total setpoint selection / Total setp sel
Access level: 4 Calculated: - Data type: U32 / Binary
Can be changed: T Scaling: - Data set: CDS, p0170
Units group: - Unit selection: -
Min Max Factory setting
- - 0
p1109[0...n] CI: Total setpoint / Total setp
Access level: 4 Calculated: - Data type: U32 / FloatingPoint32
Can be changed: T Scaling: p2000 Data set: CDS, p0170
Units group: - Unit selection: -
Min Max Factory setting
- - 0
p1110[0...n] BI: Inhibit negative direction / Inhib neg dir
Access level: 3 Calculated: - Data type: U32 / Binary
Can be changed: T Scaling: - Data set: CDS, p0170
Units group: - Unit selection: -
Min Max Factory setting
- - 1
p1111[0...n] BI: Inhibit positive direction / Inhib pos dir
Access level: 4 Calculated: - Data type: U32 / Binary
Can be changed: T Scaling: - Data set: CDS, p0170
Units group: - Unit selection: -
Min Max Factory setting
- - 0