Parameters
List of Parameters
1-164
© Siemens AG 2011 All Rights Reserved
SINAMICS G120 Control Units CU230P-2 Parameter Manual (LH9), 06/2011
Description: Sets the delay time for pulse suppression.
After OFF1 or OFF3 and zero speed detection, the system waits for this time to expire and the pulses are then sup-
pressed.
Dependency: Refer to: p1226, p1227
Note: Standstill is identified in the following cases:
- the speed actual value falls below the speed threshold in p1226 and the time started after this in p1228 has
expired.
- the speed setpoint falls below the speed threshold in p1226 and the time started after this in p1227 has expired.
Description: Sets the signal source to activate DC braking.
Dependency: Refer to: p1231, p1232, p1233, p1234, r1239
Note: 1 signal: DC braking activated.
0 signal: DC braking de-activated.
p1228 Pulse suppression delay time / Pulse suppr t_del
Access level: 3 Calculated: - Data type: FloatingPoint32
Can be changed: U, T Scaling: - Data set: -
Units group: - Unit selection: -
Min Max Factory setting
0.000 [s] 299.000 [s] 0.010 [s]
p1230[0...n] BI: DC braking activation / DC brake act
Access level: 2 Calculated: - Data type: U32 / Binary
Can be changed: U, T Scaling: - Data set: CDS, p0170
Units group: - Unit selection: -
Min Max Factory setting
- - 0