Description: Sets the source for the torque setpoint.
For single-digit values, the following applies:
The value specifies the main setpoint.
For double-digit values, the following applies:
The left-hand digit specifies the supplementary setpoint, the right-hand digit the main setpoint.
Example:
Value = 26
--> The analog setpoint (2) supplies the supplementary setpoint.
--> The fieldbus (6) supplies the main setpoint.
Value: 0: No main setpoint
2: Analog setpoint
7: Analog setpoint 2
20: Analog setpoint + no main setpoint
22: Analog setpoint + analog setpoint
27: Analog setpoint + analog setpoint 2
70: Analog setpoint 2 + no main setpoint
72: Analog setpoint 2 + analog setpoint
77: Analog setpoint 2 + analog setpoint 2
Dependency: When changing this parameter, the following settings are influenced:
Refer to: p1503, p1511
Caution: When executing a specific macro, the corresponding programmed settings are made and become active.
p1500[0...n] Torque setpoint selection / M_set sel
CU230P-2 CAN Access level: 2 Calculated: - Data type: Integer16
Can be changed: C(1), T Scaling: - Data set: CDS, p0170
Units group: - Unit selection: -
Min Max Factory setting
0 77 0