SINAMICS G120 Control Units CU230P-2 Parameter Manual (LH9), 06/2011
Description: Sets the reference quantity for speed and frequency.
All speeds or frequencies specified as relative value are referred to this reference quantity.
The reference quantity in this parameter corresponds to 100% or 4000 hex or 4000 0000 hex.
The following applies: Reference frequency (in Hz) = reference speed (in ((rpm) / 60) x pole pair number).
Dependency: This parameter is only updated during the automatic calculation (p0340 = 1, p3900 > 0) if motor commissioning was
carried out beforehand for drive data set zero. This means that the parameter is not locked against overwriting
using p0573 = 1.
Refer to: p2001, p2002, p2003, r2004, r3996
Notice: When the reference speed / reference frequency is changed, short-term communication interruptions may occur.
Note: If a BICO interconnection is established between different physical quantities, then the particular reference quanti-
ties are used as internal conversion factor.
Example 1:
The signal of an analog input (e.g. r0755[0]) is connected to a speed setpoint (e.g. p1070[0]). The actual percent-
age input value is cyclically converted into the absolute speed setpoint using the reference speed (p2000).
Example 2:
The setpoint from PROFIBUS (r2050[1]) is connected to a speed setpoint (e.g. p1070[0]). The actual input value is
cyclically converted into a percentage value via the pre-specified scaling 4000 hex. This percentage value is con-
verted to the absolute speed setpoint via reference speed (p2000).
Description: Sets the reference quantity for voltages.
All voltages specified as relative value are referred to this reference quantity. This also applies for direct voltage val-
ues (= rms value) like the DC-link voltage.
The reference quantity in this parameter corresponds to 100% or 4000 hex or 4000 0000 hex.
Dependency: p2001 is only updated during automatic calculation (p0340 = 1, p3900 > 0) if motor commissioning has been carried
out first for drive data set zero and as a result overwriting of the parameter has not been blocked by setting p0573 =
1.
Refer to: r3996
p2000 Reference speed reference frequency / n_ref f_ref
Access level: 2 Calculated: p0340 = 1 Data type: FloatingPoint32
Can be changed: T Scaling: - Data set: -
Units group: - Unit selection: -
Min Max Factory setting
6.00 [rpm] 210000.00 [rpm] 1500.00 [rpm]
p2001 Reference voltage / Reference voltage
Access level: 3 Calculated: p0340 = 1 Data type: FloatingPoint32
Can be changed: T Scaling: - Data set: -
Units group: - Unit selection: -
Min Max Factory setting
10 [Vrms] 100000 [Vrms] 1000 [Vrms]