Description: Trigger signal for the selected faults and alarms
Dependency: If one of the faults or alarms selected in p2128[n] occurs, then the particular bit of this binector output is set.
Refer to: p2128
Note: CO: r2129 = 0 --> None of the selected messages has occurred.
CO: r2129 > 0 --> At least one of the selected messages has occurred.
Description: Displays the system runtime in days when the fault occurred.
Dependency: Refer to: r0945, r0947, r0948, r0949, r2109, r2133, r2136, p8401
Notice: The time comprises r2130 (days) and r0948 (milliseconds).
The value displayed in p2130 refers to 01.01.1970.
Note: The buffer parameters are cyclically updated in the background (refer to status signal in r2139).
Description: Displays the code of the oldest active fault.
Dependency: Refer to: r3131, r3132
Note: 0: No fault present.
r2129.0...15 CO/BO: Trigger word for faults and alarms / Trigger word
Access level: 3 Calculated: - Data type: Unsigned16
Can be changed: - Scaling: - Data set: -
Units group: - Unit selection: -
Min Max Factory setting
- - -
Bit field: Bit Signal name 1 signal 0 signal FP
00 Trigger signal p2128[0] ON OFF -
01 Trigger signal p2128[1] ON OFF -
02 Trigger signal p2128[2] ON OFF -
03 Trigger signal p2128[3] ON OFF -
04 Trigger signal p2128[4] ON OFF -
05 Trigger signal p2128[5] ON OFF -
06 Trigger signal p2128[6] ON OFF -
07 Trigger signal p2128[7] ON OFF -
08 Trigger signal p2128[8] ON OFF -
09 Trigger signal p2128[9] ON OFF -
10 Trigger signal p2128[10] ON OFF -
11 Trigger signal p2128[11] ON OFF -
12 Trigger signal p2128[12] ON OFF -
13 Trigger signal p2128[13] ON OFF -
14 Trigger signal p2128[14] ON OFF -
15 Trigger signal p2128[15] ON OFF -
r2130[0...63] Fault time received in days / t_fault recv days
Access level: 3 Calculated: - Data type: Unsigned16
Can be changed: - Scaling: - Data set: -
Units group: - Unit selection: -
Min Max Factory setting
- - -
r2131 CO: Actual fault code / Actual fault code
Access level: 2 Calculated: - Data type: Unsigned16
Can be changed: - Scaling: - Data set: -
Units group: - Unit selection: -
Min Max Factory setting
- - -