User Manual

List of Parameters
Parameters
1-329
© Siemens AG 2011 All Rights Reserved
SINAMICS G120 Control Units CU230P-2 Parameter Manual (LH9), 06/2011
Description: Displays the status word of the compound braking.
Dependency: Refer to: p3856
Description: Sets the signal source to activate emergency operation (ESM = Essential Service Mode) via digital inputs.
Permissible values:
p0722.x for high-active switch-in signals
p0723.x for low-active switch-in signals
Where x = 0, 1, 2, 3, 4, 5, 11 or 12
Description: Sets the setpoint source for emergency operation (ESM).
Value: 0: Last known setpoint (r1078 smoothed)
1: Fixed speed setpoint 15 (p1015)
2: Analog setpoint AI0 (r0755[0])
3: Setpoint from fieldbus
4: Setpoint from technology controller
Warning: If the technology controller is set as the setpoint source, it must also be configured in advance. p2251 must be set
to a value of 0.
Note: When the essential service mode is activated, the effective speed setpoint is displayed in r1114.
Description: Selects the setpoint source in the event of the loss of the parameterized value from p3881.
Value: 0: Last known setpoint (r1078 smoothed)
1: Fixed speed setpoint 15 (p1015)
2: Maximum speed (p1082)
Note: Setting is only effective if p3881 = 2, 3 or 4 has been set.
r3859.0 CO/BO: Compound braking status word / Compound Br ZSW
PM240 Access level: 3 Calculated: - Data type: Unsigned32
Can be changed: - Scaling: - Data set: -
Units group: - Unit selection: -
Min Max Factory setting
- - -
Bit field: Bit Signal name 1 signal 0 signal FP
00 Compound braking active Yes No -
p3880 BI: ESM activation / ESM activation
Access level: 3 Calculated: - Data type: U32 / Binary
Can be changed: U, T Scaling: - Data set: -
Units group: - Unit selection: -
Min Max Factory setting
- - 0
p3881 ESM setp source / ESM setp source
Access level: 3 Calculated: - Data type: Integer16
Can be changed: T Scaling: - Data set: -
Units group: - Unit selection: -
Min Max Factory setting
0 4 0
p3882 ESM alternative setpoint source / ESM altern. setp
Access level: 3 Calculated: - Data type: Integer16
Can be changed: T Scaling: - Data set: -
Units group: - Unit selection: -
Min Max Factory setting
0 2 0